Specifications
© 2015 Digital Monitoring Products
Serial Num ber:
Enter the eight-digit serial number found on the wireless device.
When the panel zone stores the serial number, the panel House Code is transmitted
to that specific transmitter. This transmission is performed by the DMP Wireless
Receiver when Remote Link disconnects.
All DMP wireless programming is stored in the panel. The DMP Wireless Receiver
obtains the necessary programming information from the panel:
Each time the receiver is powered down and powered up
When a new receiver is installed
When the programmer STOP routine is selected
When the panel is reset
When Remote Link disconnects
The receiver memory refresh takes up to 45 seconds to complete depending on the
number of DMP wireless zones programmed. Normal DMP receiver operation is
inhibited during the memory refresh period.
Contact
:
1101 Universal Transmitters: Choose Internal to use the internal reed switch
contacts or choose External to connect an external contact to the 1101 terminal
block. Default is Internal.
Note: The DMP 1101 Universal Transmitter serial number may be programmed
for two zones provided the Contact type (Internal or External) is
programmed differently for each zone.
For example, program transmitter serial number 01345678 on an XT30, XT50,
XRSuper6, XR20, or XR40 panel as Zone 31 with an Internal contact type and
Zone 32 with an External contact type. The same serial number is used for
both zones.
Note: When using both contacts, you must use consecutive zone numbers.
The following list shows acceptable consecutive zone number examples:
XT30, XT50, XRSuper6, XR20, or XR40 - zones 31 and 32 or zones 34
and 41
XR550 Series or XR500 Series - zones 543 and 544 or zones 876 and 877
XR350 Series - zones 543 and 544 or zones 745 and 746
XR150 Series or XR100 Series - zones 522 and 523, or zones 596 and 597