Specifications

© 2015 Digital Monitoring Products
for two zones provided the Contact type (Internal or External) is programmed differently for
each zone.
For example, program transmitter serial number 01345678 on an XT30, XT50, XTL, XTLN,
XTLN-WiFi, XRSuper6, XR20, or XR40 panel as Zone 31 with an Internal contact type and Zone
32 with an External contact type. The same serial number is used for both zones.
Note: When using both contacts, you must use consecutive zone numbers. The following list
shows acceptable consecutive zone number examples:
XT30, XT50, XTL, XTLN, XTLN-WiFi, XRSuper6, XR20, or XR40 - zones 31 and 32 or zones 34
and 41
XR550 Series or XR500 Series - zones 543 and 544 or zones 976 and 977
XR350 Series - zones 543 and 544 or zones 741 and 742
XR150 Series or XR100 Series - zones 522 and 523, or zones 596 and 597
Contact N/O: Select this option to indicate an external device connected to the 1101 terminal block is
programmed to use a normally open (N/O) contact. Leave this box not checked to use a normally
closed (N/C) contact.
1114 Wireless Four-Zone Expander
The same Serial Number is used for all four contacts. Choose Contact 1, 2, 3, or 4.
Note: When using the contacts, you must use consecutive zone numbers. For example, use
serial number 08345678 on an XR100 or XR500 Series panel to program Contact 1 for Zone
561, Contact 2 for Zone 562, Contact 3 for zone 563, and Contact 4 for zone 564.
The following list shows acceptable consecutive zone number examples:
XT30, XT50, XTL, XTLN, XTLN-WiFi, XRSuper6, XR20, or XR40 - zones 31, 32, 33, and 34 or
zones 41, 42, 43, and 44
XR550 or XR500 Series - zones 543, 544, 545, and 546 or zones 976, 977, 978, and 979
XR350 Series - zones 543, 544, 545, and 546 or zones 741, 742, 743, and 744
XR100 Series - zones 522, 523, 524, and 525 or zones 596, 597, 598, and 599
Note: A tamper on the 1114 is transmitted as the zone number assigned to Contact 1.
Supervision Time: Select the supervision time required for the wireless zone. The wireless
transmitter must check-in at least once during this time or a missing condition is indicated for that
zone. DMP 1100 Series transmitters automatically check-in based on the supervision time selected for
the wireless zone, no additional programming is needed. If two zones share the same transmitter, the
last programmed supervision time is stored as the supervision time for both zones. Select 3, 60, or
240 minutes. On XR150/XR350/XR550 Series, XR100/XR500 Series Version 207 or higher, XT30/XT50
Version 106 or higher, XTL, XTLN, and XTLN-WiFi panels, the 3 minute Supervision Time can only be
selected if the zone type is fire, fire verify, or supervisory. Select None for unsupervised operation.
Default is 240 minutes.
Note: When the panel is reset or a receiver is installed or powered down and powered up, or
Remote Link disconnects, the supervision timer restarts for all wireless zones.
LED Enabled: Select this option to turn on a panic, pendant, or hold-up transmitter LED during Panic
or Emergency operation. The LED always operates when the transmitter case is open and the tamper is
faulted.
Note: When any wireless input zone for a particular address is programmed (Ex: 11-14 = Addr
1 on the Keypad Bus or 586 on an XR500 Series or XR100 Series LX-Bus), the DMP receiver
responds to the panel for this address. Other devices, such as keypads or hardwired zone