Specifications

© 2015 Digital Monitoring Products
Step: When programmed as an Area system, a short will arm the areas and beep the keypads
once. When programmed as All/Perimeter or Home/Away, on the first short Home (Perimeter) will
arm and beep the keypads once. On the second short, Sleep will arm for Home/Away systems and
beep the keypads twice. When programmed as All/Perimeter, the interior will arm and beep the
keypads twice. On the third short, Away will arm and beep the keypads three times. A normal
condition will cause no action. An open condition will disarm the programmed areas and beep the
keypads for one second.
Note: This arming style is designed for wireless arming pendants. When using an arming/
disarming keyswitch locate the keyswitch within the protected area.
Maintain: When the zone is shorted, the programmed areas are armed. When restored to normal,
the programmed areas are disarmed and any alarm bells are silenced. When the zone is opened
from a normal (disarmed) state, a trouble is reported. If opened from a shorted (armed) state, an
alarm is reported and the zone is disabled until you disarm the area(s) from either a keypad or
Remote Link computer.
Program > Zo ne Informatio n > Standard Tab
Zone Number: Enter the number of the zone you are programming.
XR550 Series, XR500 Series, XR2500F Zone Numbers
XR350 Series Zone Numbers
XR150 Series, XR100 Series Zone Numbers
XT Series Zone Numbers
XRSuper6, XR20, XR40 Zone Numbers
XR200, XR200-485(B), XR2400F Zone Numbers
Zone Name: Assign a name to each zone in the system. Zone names may have up to 32 alphanumeric
characters. The name can display at the keypads during arming and disarming so the user does not
have to memorize zone numbers.
Type: This field designates the zone type, which defines the panel's response to the zone being
opened or shorted, or the Alarm Action.
Area: Enter the area number where you are assigning the zone. In an Area system or a Home/Sleep/
Away with Guest system, enter the area number where this zone is being assigned. Area numbers can
be assigned for Night, Day, Exit, Auxiliary 1 and Auxiliary 2 zones.