Specifications
© 2015 Digital Monitoring Products
set to NO, the Interior area auto disarm does not occur if an exit zone is not tripped during
the exit delay time.
Bank Safe & Vault: When this option is selected, the area can only be disarmed during scheduled
times. Not selecting this box will disable Bank Safe & Vault mode for this area.
Note: Do not assign Bank Safe & Vault areas to an Arming zone. Arming zones can disarm
Bank Safe & Vault areas outside of a schedule.
Common Area: Selecting this box will enable the area to operate as a common area. This area is
armed when the last area in the partition is armed and is disarmed when the first area in the partition
is disarmed. You can have multiple common areas in each partition.
Two Man Rule: Checking this box will require two user code entries to disarm or allow door access in
this area. When a user presents a code to a keypad or reader requesting door access or disarm, the
keypad will display "2ND CODE". A second user code with at least the same authority must be entered
to allow entry or to disarm.
Arm First: Enables the area to operate as an Arm First area. This area automatically arms when any
non-Arm First area assigned to the same keypad is armed but does not disarm when other areas
become disarmed. If an Arm First area has faulted zones that cannot be bypassed, arming stops.
Default value is NO.
Description: Enter a note about the area that you are programming. To enter a note or description,
press the Description button to open the Edit Rich Text window. After you type your note, go to File >
Save and Exit to save your work and close the Edit Rich Text window. Your note appears in the field
above the Description button.
Program > Area Informatio n > Global Settings
Exit Delay: Enter the exit delay time for all Exit type zones in this area. When the exit delay time
starts, all activity on that zone and other non-24-hour zone types in the area is ignored until the exit
delay expires. The keypad displays the Exit Delay time countdown and annunciates the Exit Delay tone
at 8 second intervals until the last 10 seconds when annunciation is at 3 second intervals.
The exit delay can be from 30 to 250 seconds. Default is 60 seconds.
During Exit Delay, if an exit zone trips, then restores, and trips again, the Exit Delay timer
restarts. This restart can occur only once.
Burglary Bell Output: Enter the output number that is turned on any time a Burglary type zone in this
partition goes into alarm. The output is turned off when you disarm the area where the alarm
occurred and no other Burglary type zones are in alarm. The Burglary Bell Output can also be turned
off at the keypad using the Alarm Silence option in the User Menu or by entering a user code with the
authority to silence alarms. The duration of the bell output follows the time entered in the Bell Cutoff
Time field in the Output Options window.
Early Morning Ambush (XR150/XR350/XR550 with Network and XR500 with Network only):
Enter the number of minutes delay, from 1 to 15, before a silent alarm (Early Morning Ambush S33