Specifications

© 2015 Digital Monitoring Products
Battery Power
Closing Check
Panel Box Tamper
Phone Line 1
Phone Line 2
Wireless Receiver Trouble
Wireless Jamming Trouble or Alarm
Fire Zone Keypads: Specifies the keypad addresses to display all fire zone alarms and troubles. The
zone name is displayed on the keypad and, if it is a trouble condition, a steady trouble buzzer will
sound at the keypad.
Burglary Zone Keypads: Specifies the addresses where all burglary zone alarms and troubles are
displayed. Burglary zones include Night, Day, and Exit type zones. Burglary zone troubles remain in the
list until the zone restores.
Supervisory Zone Keypads: Specifies the addresses where all supervisory zone alarms and troubles
are displayed. When the keypad displays a supervisory zone, the keypad buzzer will sound. To silence
the keypad buzzer, enter a valid user code at the keypad.
Panic Zone Keypads: Specifies the addresses where all panic zone alarms and troubles are displayed.
The name of the zone remains in the list until the zone restores. The keypad buzzer does not sound
for panic alarms or troubles.
Emergency Zone Keypads: Specifies the addresses where all emergency zone alarms and troubles
are displayed. The name of the zone remains in the list until the zone restores. The keypad buzzer
does not sound for emergency alarms or troubles.
Auxiliary 1 Zone Keypads: Specifies the addresses where all Auxiliary 1 zone alarms and troubles are
displayed. The name of the zone remains in the list until the zone restores. The keypad buzzer does
not sound for Auxiliary 1 alarms or troubles.
Auxiliary 2 Zone Keypads: Specifies the addresses where all Auxiliary 2 zone alarms and troubles are
displayed. The name of the zone remains in the list until the zone restores. The keypad buzzer does
not sound for Auxiliary 2 alarms or troubles.
Communication Path Trouble: Specifies the way communication path troubles are displayed on
keypads programmed to display system troubles.
Select NO to not display communication path troubles on any keypad.
Select YES to display COMM -TRBL when any communication path fails.
Select ALL to display COMM -TRBL only when all communication paths have failed.
Program > Printer Reports
This section allows you to program the types of reports the panel will print using the optional Printer
Interface Card. The Printer Interface Card allows you to connect a compatible 40 or 80 character serial
printer to the alarm panel.
The options you may select in the Printer Reports window are:
Arm / Disarm Reports: Prints arming, disarming, and Late to Close reports. Reports include the
area number, name, and action (armed, disarmed, or late), the user number, user name, and time
and date.