Specifications
© 2015 Digital Monitoring Products
Program > Output Options
Program individual outputs to
activate for various events.
Enter 0 (zero) to disable any
output. Refer to Bell Options
section to select bell actions.
Communication Fail Output:
Assign the number of the
output that you want to
activate when either of the
following conditions occur:
A Digital Dialer (DD)
system fails to
communicate on three
successive dial
attempts.
A Multiplex (MPX)
system does not
communicate with the
receiver for 150
seconds, or if the backup communication line transmits a report.
To reset a Communications Fail Output, disarm any area.
Ready Output: Enter the output number to turn on when all disarmed burglary zone types are in a
normal state. The output turns off when any disarmed burglary type zone is in a bad state. This output
is not compatible with Cutoff Outputs.
Phone Trouble Output: Enter output number to turn on when the phone line monitor in the DMP
893/893A detects a voltage below 3 VDC or when the short across pins 2 and 7 on the phone block is
open. The output is turned off when phone voltage rises above 3 VDC. Enter zero to disable this
output.
Device Fail Output: Enter output number to turn on when an addressed device fails to respond to
polling from the panel. The panel also sends a missing device report to the receiver. The output is
turned off when the device reported as missing responds to polling or is removed from the system.
Enter 0 (zero) to disable this output and the LX-Bus device fail reporting to the central station.
The Device Fail Output option should not be used if the system has any unsupervised devices.
Note: Remote Link displays the first Device Missing message. Subsequent Device Missing
messages are incremented on the repeat counter and do not display individually.
Sensor Reset Output: Enter the output number to turn on when a Sensor Reset is performed. The
output automatically turns off after five seconds. This function can be used to reset smoke detectors
that are operated by an external power supply through an optional Model 716 Output Expander Module.