Specifications

© 2015 Digital Monitoring Products
Program > Output Options
Panic Output: Enter the output number to turn on when any Panic type zone is placed in an alarm
condition. The output is turned off after all Panic zones are restored from an alarm condition and a
Sensor Reset is performed.
Wireless Outputs:
The Panic Alarm is compatible with the Model 1118 Wireless Remote Indicator Light and the Model
1116 Wireless Relay Output connected to a Model 572 Indicator LED.
When a Panic Test is initiated from the keypad, the LED flashes quickly for five minutes.
When a Panic Alarm occurs, the LED turns on steady for five minutes and then turns off.
For a Panic Alarm, a fast response wireless output number is recommended.
Phone Trouble Output: Enter the output number to turn on when the phone line monitor in the DMP
893A detects a voltage below 3 VDC on the phone block. The output is turned off when phone voltage
rises above 3 VDC.
Device Fail Output: Enter output number to turn on when an addressed device fails to respond to
polling from the panel. The panel also sends a missing device report to the receiver. The output is
turned off when the device reported as missing responds to polling or is removed from the system.
Enter 0 (zero) to disable this output and the LX-Bus device fail reporting to the central station.
The Device Fail Output option should not be used if the system has any unsupervised devices.
Note: Remote Link displays the first Device Missing message. Subsequent Device Missing
messages are incremented on the repeat counter and do not display individually.
Closing Wait Output: Enter the output number to turn on for four (4) seconds when Closing Wait is
programmed as YES and the closing message is communicated successfully at arming. If the closing
message does not communicate successfully, this output does not turn on. Additionally, if Bell Test is
programmed as YES and the panel successfully communicates the closing message, the output turns on
before the Bell Test starts and turns off after the Bell Test ends.
Supervisory Alarm Output: Enter the output number to turn on when a supervisory zone type is
placed into an alarm. The output turns off when all supervisory type zones are restored to normal.
Enter 0 (zero) to disable. Default is 0.