Specifications

© 2015 Digital Monitoring Products
are in a normal state. The output turns off when any disarmed burtoff Outputs.
Telephone Trouble Output: Enter the output number to turn on when the phone line monitor on the
panel phone line is lost. Enter 0 (zero) to disable this output.
Late to Close Output: Enter the output/Favorite number to turn on at the expiration of a closing
schedule. The output activates simultaneously with the "CLOSING TIME!" keypad display. The output
turns off when the late area is armed, the closing is extended, or the schedule is changed.
Note: The Late to Close Output option is not available on XRSuper6 panels.
Armed Output: Enter the output/Favorite number to turn on any time an area of the system arms.
The output turns off when the system completely disarms. Enter 0 (zero) to disable this output.
Favorites:
For a Home/Away system:
When the system is armed AWAY, the programmed Favorite activates.
When the system is armed SLEEP, the programmed Favorite plus 1 is activated. For example,
If the Armed Output is F05, F06 activates when Sleep is armed.
When the system is armed HOME, the programmed Favorite plus 2 is activated. For example,
If the Armed Output is F05, F07 activates when Home is armed.
For an All/Perimeter system:
When the system is armed ALL, the programmed Favorite activates.
When the system is armed PERIMETER, the programmed Favorite plus 1 is activated.
For example, If the Armed Output is F05, F06 activates when Perimeter is armed.
For an Area system:
When any area of the system is armed, the programmed Favorite activates.
Disarmed Output: Enter the output/Favorite number to turn on when all areas of the panel are
disarmed. The output turns off when the an area is armed. Enter 0 (zero) to disable this output.
Burglary Output: Enter the output/Favorite to turn on any time a burglary zone goes into alarm. The
output turns off when the area in which the alarm occurred disarms and no other burglary zones are in
alarm. Enter 0 (zero) to disable this output.
Arm-Alarm Output: Enter the output/Favorite number to turn on steady when any area of the system
is armed. If an alarm occurs causing the keypads to turn Red, this output pulses and continues to pulse
for approximately three (3) minutes after the panel is disarmed.
Wireless Outputs:
The Arm-Alarm Output is compatible with the Model 1117 Wireless LED Annunciator and the
Model 1116 Wireless Relay Output connect to a Model 572 Indicator LED.
When the Model 1117 is battery operated the LED is off when the system is armed to
conserve battery life. If an alarm occurs, the output flashes quickly.
When the Model 1116 is connected to a Model 572 LED annunciator, the LED is on when the
system is armed. If an alarm occurs, the output pulses.
Note: The Arm-Alarm Output option is available on XR150/XR350/XR550 Series, XR100/XR500
Series, XR2500F, XT30, XT50, XRSuper6, XR20, and XR40 panels.
Bell Options
Additional Options for XT30 and XT50
Additional Options for XRSuper6, XR20, XR40
Additional Options for XR150/XR350/XR550 Series and XR100/XR500 Series, XR2500F