Communication Fail Output: Assign the number of the output/Favorite that you want the panel to
activate when the Digital Dialer (DD) system fails to communicate on three successive dial attempts.
Communication Fail Output can also be used for the XR200, XR200-485(B), XR2400F or iCOMsl. See
Additional Outputs for XR200, XR200-485(B) and XR2400F Panels or, Outputs for iCOMSL section.
To reset a Communications Fail Output, disarm any area.
Fire Alarm Output: Enter the output/Favorite number to turn on when a fire type zone is placed in
alarm. The output turns off when a Sensor Reset is performed if no additional fire type zones are in
alarm.
Fire Alarm Output is not compatible with Cutoff Outputs.
Fire Trouble Output: Enter the output/Favorite number to turn on when a fire type zone is placed in
trouble or when a supervisory type zone (AC Trouble, Battery Trouble, or Phone line 1 or 2) is placed in
trouble. The output turns off when all fire and supervisory type zones are restored to normal.
An output assigned as a Fire Trouble Output cannot be assigned as a Cutoff Output.
Panic Alarm Output: Enter the output/Favorite number to turn on when any Panic type
zone is placed in an alarm condition. The output is turned off after all Panic zones
are restored from an alarm condition and a Sensor Reset is performed. Enter 0
(zero) to disable.
Wireless Outputs (XT30, XT50, XTL, XTLN, or XTLN-WiFi)
If a wireless output is programmed, the panel sends the Panic Test Cadence or the Panic
Alarm Cadence to the output when a Panic Test is performed or a Panic Zone is placed in
alarm.
Wireless Outputs (XR150/XR350/XR550 Series, XR100/XR500 Series)
The Panic Alarm is compatible with the Model 1118 Wireless Remote Indicator Light and the
Model 1116 Wireless Relay Output connected to a Model 572 Indicator LED.
• When a Panic Alarm occurs, the LED turns on steady for five minutes and then turns off.
• When a Panic Test is initiated from the keypad, the LED flashes quickly for five minutes.
• For a Panic Alarm, a fast response wireless output number is recommended.
Ambush Output: Enter the output/Favorite number to turn on when an Ambush code is entered at a
keypad. The output turns off when a Sensor Reset is performed.
Entry Output: Enter the output/Favorite number to turn on at the start of the entry delay time. The
output turns off when the area disarms or the entry delay time expires.
Exit Output: Enter the output/Favorite number to turn on when an exit delay time starts in any area
of the system. The output turns off when the area arms or when the arming stops.
Begin Exit Output (XR150/XR350/XR550 Series, XT30, XT50, XTL Version 110 or higher only,
and XTLN/XTLN-WiFi): Enter the output or Favorite number to turn on when an exit delay time starts
in any area of the system. The output turns off when the area arms or when the arming stops.
End Exit Output (XR150/XR350/XR550 Series, XT30, XT50, XTL Version 110 or higher only,
and XTLN/XTLN-WiFi): Enter the output or Favorite number to turn on when an exit delay time ends
in any area of the system. The output turns off when the system disarms.
Ready Output: Enter the output/Favorite number to turn on when all disarmed burglary zone types