Specifications

© 2015 Digital Monitoring Products
Emergency Bell Action Emergency Type zones
Aux 1 Bell Action Auxiliary 1 Type zones
Aux 2 Bell Action Auxiliary 2 Type zones
Miscellaneous Options
Bell Cutoff Time: Enter the maximum time for the bell output to remain on. If the bell output is
manually silenced or the area is disarmed, the cutoff time is reset. Enter 0 (zero) to provide
continuous bell output. Default is 15 minutes unless otherwise noted.
XT30, XT50, XTL, XTLN, XTLN-WiFi - select 1 to 15 minutes (Default is 5)
Note: The XTL/XTLN/XTLN-WiFi does not allow 0 (zero) to be entered in Bell Cutoff Time.
XRSuper6, XR20, XR40 - select 1 to 15 minutes
XR150/XR350/XR550 Series, XR100/XR500 Series, XR2500F - select from 1 to 99 minutes
XR200, XR2400F, or XR200-485(B) - select from 1 to 99 minutes
Automatic Bell Test: When this box is selected, the bell output is turned on for two seconds each
time an area is completely armed from a keypad.
The automatic bell test is delayed until the Closing Wait acknowledgement is received (if selected). If
the Closing Wait acknowledgement is not received within 90 seconds, the bell test will not occur. If
Closing Wait is not selected in the System Options window, the automatic bell test occurs when the
last area arms.
A bell test only occurs when the areas are armed from a keypad. Arming performed from an arming
zone or remotely from Remote Link does not activate a bell test.
Bell Output: Enter the output number when needed to follow the panel bell output operation for all
actions and off conditions on XR150/XR350/XR550 Series, XR100/XR500 Series, XR2500F, XRSuper6,
XR20, or XR40 panels. Enter 0 (zero) to disable the output.
Bell Output (XT30/XT50/XTL/XTLN/XTLN-WiFi): Enter the output/Favorite number to follow the
panel bell terminal 5 operation for all action and off conditions. Enter 0 (zero) to disable the output.
Note: When BELL ACTION is set to T for Temporal Code 3, the output action is Pulse when
connected to:
-an LX-Bus output on an XR150/XR350/XR550 Series, XR100/XR500 Series, or XR2500F panel.
-an output on an XT30, XT50, XRSuper6, XR20, or XR40 panel.
Note: Bell Output should not be programmed for a Model 1135/1135DB Wireless Siren when
programmed in Output Information to Trip with Panel Bell.
Program > Output Options
The Output Options window allows you to assign individual outputs to activate for various events. The
Output Options window also enables you to set the Cutoff Outputs, Output Cutoff Time, and the Heat