Specifications

© 2015 Digital Monitoring Products
Program > System Options
iCOMsl Options
Keypad Mode: Select Keypad Mode to allow the iCOMsl to operate in Keypad Mode on the keypad bus
of an XR20 (version 203 and above) or XR40 (version 203 and above). In Keypad Mode the iCOMsl
sends messages for all panel zones and provides more detailed message information.
To program the iCOMsl to operate in Input Mode, do not select Keypad Mode. When programmed for
Input Mode, the iCOMsl can be used for slave applications or stand-alone applications. Refer to the
iCOMsl Installation (LT-0631) for more information.
Program > Bell Options
The Bell Options window allows you to specify what type of alarm output the panel initiates for
different types of alarms.
Options
There are three types of alarm output available Steady, Pulse, and Temporal (Code 3). Selecting None
for an alarm event will cause no alarm to sound for the specified type of alarm.
Action Zone Type
Fire Bell Action Fire Type zones
Burglary Bell Action Burglary Type zones and Exit Error output
Supervisory Bell Action Supervisory Type zones
Panic Bell Action Panic Type zones