Specifications
© 2015 Digital Monitoring Products
Program > System Options
Entry Delay 1: Enter the Entry Delay time for all exit-type zones
programmed to use Entry Delay 1. When an armed Exit type zone is
faulted, the keypad prewarn tone sounds and "ENTER CODE: -"
displays on all keypads programmed to prewarn for that zone. The
area must be disarmed before the delay expires or an alarm report is
sent to the receiver. Entry Delay times can be from 1 to 250 seconds.
Note: Program Entry Delay 2, 3, and 4 following Entry Delay 1
instructions.
Zone Retard Delay: Enter the retard time assigned to Fire,
Supervisory, Auxiliary 1, and Auxiliary 2 type zones. The retard delay
only functions when the zone is shorted. The zone must remain
shorted for the entire length of the Retard Delay before being recognized by the panel. The Zone
Retard Delay can be from 1 to 50 seconds. Entering a zero disables this feature.
Note: In the XR200 and XR2400F version 112 and higher, and the XR200-485 version 206 and
higher, if the zone is programmed as an Auxiliary 2 or Arming type, the Zone Retard Delay
timer is counted in minutes.
The number entered for Zone Retard Delay will be used for all types of zones that are
programmed for Retard in Zone Information. For example, it you enter a 15 second delay for
Fire zones, there will be a 15 minute delay for Auxiliary 2 and Arming type zones.
Program > System Options
Hours from GMT: Enter the Greenwich Mean Time (GMT) zone where the panel is located. For
example, Central Standard Time would be entered as 6. Please see the table of time zones to help
locate the appropriate time zone.
Allow Time Change: When this box is checked, the panel requests time updates from the receiver.
Cross Zone Time: Enter the time allowed between zone faults. When zones are cross zoned, the same
zone or a second cross zoned zone must fault within this time in order for an alarm report for both
zones to be sent to the receiver. If the cross zone time expires without the second zone faulting, only
a zone fault from the first zone is reported.
Cross-zone time can be from 4 to 250 seconds. Entering 0 (zero) disables this function.