Specifications
© 2015 Digital Monitoring Products
must remain shorted for the entire length of the Retard Delay before being recognized by the panel.
The Zone Retard Delay can be from 1 to 250 seconds. Entering a zero disables this feature.
Note: The number entered for Zone Retard Delay will be used for all types of zones that are
programmed for Retard in Zone Information. For example, it you enter a 15 second delay for
Fire zones, there will be a 15 minute delay for Auxiliary 2 and Arming type zones.
Power Fail Delay: Tracks the duration of an AC power failure. When the AC power is off for the
length of the programmed delay time, an AC power failure report is sent to the receiver. The delay
time can be from 1 to 15 hours. If you enter a 0 (zero), the panel sends the AC power failure report
after a 15-second delay.
Program > System Options
Miscellaneous Options
Miscellaneous Options - XR500 Series
Miscellaneous Options - XR550 Series
Swinger Bypass Trips: Enter the number of times a zone can go into an alarm or trouble condition
within one hour before being automatically bypassed. Bypassed zones are automatically reset
whenever the area they are assigned to is disarmed. All 24-hour zones are reset when any area of the
system is disarmed. Entering 0 (zero) disables this function.
XT30/XT50
CellComSL
XR500 Series/XR100 Series Version 206 or lower - select 1 to 2 trips
XR500 Series/XR100 Series Version 207 or higher - select 1 to 6 trips
XR150/XR350/XR550 Series - select 1 to 6 trips
XR200, XR200-485(B), XR2400F - select 1 to 7 trips
Note: The panel hour timer starts at 59 minutes past the hour. If the hour timer expires
before the trip counter is exceeded, the trip counter returns to zero. If the trip counter is
exceeded before the hour expires, the panel automatically bypasses the zone. A report of the
automatic bypass is sent to the receiver if Bypass Reports is checked in Program > System