zone. See Exit Delay.
Exit Delay: Enter the exit delay time for all Exit type zones. When the exit delay time begins all
activity on exit and burglary zones is ignored until the exit delay expires. The keypad displays the Exit
Delay time countdown and annunciates the Exit Delay tone at 8 second intervals until the last 10
seconds when annunciation is at 3 second intervals. The exit delay can be from 45 to 250 seconds.
Default is 60 seconds.
Note: For XR100/XR500 Version 200 or lower, when the SIA CP-01 option in System Options is
not enabled, the exit delay progress countdown displays but annunciation does not occur.
During Exit Delay, if an exit zone trips, then restores, and trips again, the Exit Delay timer restarts.
This restart can occur only once.
Note: When Communication Type is NET, the Exit Delay restart does not occur.
Exit Error Operation: At arming, when an entry/exit zone (EX) is faulted at the end of the exit delay
then one of two sequences occur:
For Entry Delay 1 EX type zones:
the bell sounds for the length of time set in Bell Cutoff programming
the Entry Delay operation starts, requiring code entry to disarm
if not disarmed, a zone alarm and an Exit Error are sent to the receiver
For Entry Delay 2 EX type zones:
the zone is force armed and a zone force arm message is sent to the receiver
an Exit Error is sent to the receiver
the bell sounds for the length of time set in Bell Cutoff programming
Note: For XR100/XR500 Version 200 or lower, when the SIA CP-01 option in System Options
not enabled, both Entry Delay 1 and 2 operate as described for Entry Delay 2 above.
Program > System Options
SIA CP-01: When selected, the panel operates according to SIA CP-01 standards for the following
operations:
Power Up and Stop Routine - the 60 second zone startup delay is turned on.
Keypress Alarm Silence - during an alarm, the keypad alarm and bell output turn off when the
first key is pressed at a keypad.
Entry Delay - entering the first digit of a code at the keypad stops the prewarn tone.
Exit Delay - the keypad displays the Exit Delay time countdown and annunciates a tone at 8
second intervals until the last 10 seconds when annunciation is at 3 second intervals.
Exit Error Operation
When the exit zone is faulted (door still open) at the end of the exit delay:
- the bell sounds for the length of time set in Bell Cutoff programming
- the Entry Delay operation starts, requiring code entry to disarm
- if not disarmed, a zone alarm and an Exit Error are sent to the receiver