Specifications
© 2015 Digital Monitoring Products
XR150/XR350/XR550 Series, XR100/XR500 Series System Options follow. System Options for the
iCOMSL are last.
Hours from GMT: Enter the Greenwich Mean Time (GMT) zone where the panel is located. For
example, Central Standard Time would be entered as 6. Please see the table of time zones in the
Appendix to help locate the appropriate time zone.
Allow Time Change: When this box is checked, the panel requests time updates from the receiver.
Cross Zone Time: Enter the time allowed between zone faults. When zones are cross zoned, the same
zone or a second cross zoned zone must fault within this time in order for an alarm report for both
zones to be sent to the receiver. If the cross zone time expires without the second zone faulting, only
a zone fault from the first zone is reported.
Cross-zone time can be from 4 to 250 seconds. Entering 0 (zero) disables this function.
Power Fail Delay: Tracks the duration of an AC power failure. When the AC power is off for the
length of the programmed delay time, an AC power failure report is sent to the receiver. The delay
time can be from 1 to 15 hours. If you enter a 0 (zero), the panel sends the AC power failure report
after a 15-second delay.
Options for XRSuper6, XR20, XR40 Panels
Delays for XRSuper6, XR20, XR40 Panels
Miscellaneous Options for XRSuper6, XR20, XR40 Panels
Options for XR500 Series, XR100 Series, and XR200 Panels
Options for XT30/XT50, XTL, XTLN, XTLN-WiFi, XRSuper6, XR20, XR40 Panels
Miscellaneous Options for XR500 Series, XR100 Series, and XR200 Panels
Additional Options for XR150/XR350/XR550 Series, XR2500F, and XR100/XR500 Series Panels
Delays for XR500 Series, XR2500F, and XR100 Series Panels
Delays for XR200, XR200-485(B), XR2400F Panels
Options for iCOMsl
Time Change for all Panels
Time Zone Table for all Panels
Advanced Options for XR200, XR200-485(B), XR2400F, XR500 Series, XR2500F Panels
Program > System Options >
Cross Zone Time: Enter the time allowed between zone faults. When zones are cross zoned, the same
zone or a second cross zoned zone must fault within this time in order for an alarm report for both
zones to be sent to the receiver. If the cross zone time expires without the second zone faulting, only
a zone fault from the first zone is reported. Cross-zone time can be from 4 to 250 seconds. Entering 0
(zero) disables this function.
Power Fail Delay: Tracks the duration of an AC power failure. When the AC power is off for the
length of the programmed delay time, an AC power failure report is sent to the receiver. The delay
time can be from 1 to 15 hours. If you enter a 0 (zero), the panel sends the AC power failure report
after a 15-second delay.