Specifications
© 2015 Digital Monitoring Products
For XR150/XR350/XR550 Series, XR500 Series and XR2500F panels Version 110 or higher, if the area
where the alarm occurred is disarmed after the alarm message has been sent to the receiver but
before the bell cutoff time expires even if the alarm was silenced, an Cancel Signal Received (S49)
message is sent. The Cancel Signal Received report cannot be disabled.
Note: The panel sends a "Warning: Alarm Bell Silenced" report to the central station if a user
silences the alarm bell from a keypad.
Abort reports are also sent when the system is disarmed during transmit delay while the bell output
timer is active.
Note: For XR150/XR350/XR550 Series, XR500 Series, XR2500F panels Version 110 or higher,
and XR100 Series, if the area where the alarm occurred is disarmed before the alarm message
has been sent to the receiver during transmit delay and before the bell cutoff time expires
even if the alarm was silenced, an Abort Signal (S45) message is sent.
If the area where the alarm occurred is disarmed after the alarm message was sent and before the bell
cutoff time expired, a Cancel Signal (S49) message is sent. The Cancel Signal message cannot be
disabled.
Bypass Reports: Checking the Bypass Reports box sends all zone bypasses, resets, and force arm
reports to the receiver. The bypass report includes the zone number, zone name, and the user name
and number of the individual operating the system.
Schedule Change Reports: Checking the Schedule Change Reports box sends all schedule changes to
the receiver. The report includes the day, opening time, and closing time. In addition, the Schedule
Change feature will send the user name and number of the individual making these changes. Schedule
changes made through Remote Link are not sent to the printer or the event buffer.
Code Change Reports: Checking the Code Change Reports box sends all code additions, changes,
and deletions to the receiver. The code change report includes the user name and number added or
deleted and the user name and number of the individual making the change. Code changes made
through Remote Link are not sent to the printer or the event buffer.
Ambush: Checking this box sends an ambush report to the central station whenever user code number
one is entered at a keypad. If you leave this box empty, the panel does not send ambush reports, and
user number one becomes a standard user code instead of an ambush code.
Late To Open (XT30/XT50, XTL, XTLN, and XTLN-WiFi only): Enter 1-240 as the number of minutes
to elapse that the system may remain armed after the opening time of a schedule without sending a
Late To Open message. If the system continues to be armed after the Late to Open minutes expire, a
Late To Open message is sent to the central station. Default is 0, which disables the Late To Open
option.
Early To Close (XT30/XT50, XTL, XTLN, XTLN-WiFi only): Enter 1-240 as the number of minutes
that the system can be armed prior to the scheduled closing time. If the system is armed prior to the
Early to Close minutes, an Early To Close message is sent to the central station. Default is 0, which
disables the Early To Close option.
Program > System Options
The System Options window allows you to configure options that apply across the entire system.
System Options information is grouped for related panels. Options for all panels are listed first. The
XT30, XT50, XTL, XTLN, XTLN-WiFi, XRSuper6, XR20, and XR40 panel System Options are next. The