Specifications
© 2015 Digital Monitoring Products
Zone 2 Options
Activate Zone 2 Bypass: Select to enable the Bypass option. Disabling allows standard zone
operation on Zone 2. Default setting is disabled.
If the door being released by the 734/734N/734N-WiFi module is protected (contact installed), you can
provide a programmable Bypass entry/exit timer by connecting its contact wiring to the
734/734N/734N-WiFi module Zone 2. When the on-board Form C relay activates and the user opens
the door connected to Zone 2, the zone is bypassed for the number of seconds programmed in Zone 2
Bypass Time allowing the user to enter/exit.
If Zone 2 does not restore (door closed) within the programmed bypass time, the 734 piezo pulses
during the last ten seconds. If Zone 2 restores prior to the end of the programmed time, the piezo
silences. If the zone does not restore before the programmed time, the 734/734N/734N-WiFi ends the
bypass and indicates the open or short zone condition to the panel.
Relock on Zone 2 Change: Select to turn the 734 door relay off and relock the door when Zone 2
changes state. Disabling this option leaves the relay on for the door access time when Zone 2 restores.
The default is disabled.
Zone 2 Bypass Time: Enter the number of Bypass seconds to elapse before the Bypass timer
expires. Range is from 20 to 250 seconds. If the door remains open when the timer expires a zone
open/short is sent to the panel for Zone 2. The default is 40 seconds.
Zone 3 Options
Activate Zone 3 Request to Exit: Selecting enables the Zone 3 Request to Exit (REX) option.
Disabling allows standard zone operation on Zone 3. Default setting is disabled.
Optionally connect a PIR (or other motion sensing device) or a mechanical switch to Zone 3 to provide
REX capability to the system. When Zone 3 shorts, the on-board Form C relay activates for the
programmed number of seconds. During this time, the user can open the protected door to start the
programmed Bypass entry/exit timer. After the programmed number of seconds, the relay restores
the door to its locked state.
The 734/734N/734N-WiFi module provides a bypass-only option for REX on Zone 3. When Zone 3 opens
from a normal state, only a bypass occurs: the on-board relay does not activate. This bypass-only
option uses two methods of REX. The first REX device provides the programmed Bypass entry/exit
timer. The second REX device, or manual device such as a door knob, unlocks the door.
An example of the shunt-only configuration is a door to an office that is locked 24 hours a day. Users
pass a REX motion detector positioned by the door to begin the programmed exit timer. Within the
programmed number of seconds the user must then manually activate a second device, such as a REX
device or manual door knob, to unlock the door. If the door is opened after the programmed number
of seconds, the zone goes into alarm.