Specifications

© 2015 Digital Monitoring Products
and alarms only for zones assigned to those areas. When arming/disarming from Device 1, only areas
20, 21, and 22 may be armed/disarmed, even when the User Profile has authority to arm/disarm other
system areas.
Exception: Disarming of other areas not selected in Display Areas can be accomplished by presenting a
card that has disarming authority and matching profile areas with areas assigned in Device Access
Areas.
Strike Time: This option displays if DOOR is selected as Device Type.
Enter the length of time that a keypad or access control device relay will be activated. Magnetic locks
or electric door strikes can be connected to the relay and released for the length of time specified
here. Enter a time between 1 and 250 seconds. The default is 5 seconds.
You can enter 0 to activate the device relay with a toggle action. This allows the user to activate or
deactivate the device relay each time a valid user code is entered. The device relay is activated or
deactivated until a user code is entered again.
Note: The Request to Exit door access time of a keypad or Model 733 or 734/734N Wiegand
Interface Module is not affected by this selection. The Request to Exit time will remain at 5
seconds.
Strike Delay (XR150/XR350/XR550 Series and XR100/XR500 Series): This option displays if
DOOR is selected as Device Type.
Enter the number of minutes, 0 to 9, to delay a door strike after a valid code is entered or a card read
occurs. When a valid card read or code is received, the activation of the door strike is delayed for the
number of minutes programmed. The standard door strike message is sent to the Central Station
receiver and logged in the Display events at the time of card read or code entry and is not delayed.
During this delay, all subsequent codes entered or cards presented to the reader for a door strike are
ignored and no record of the attempt is stored. Enter zero to disable. Default is 0 (zero).
Fire Exit: This option allows the door access relay at this address to be released whenever fire panic
keys are pressed or a Fire or Fire Verify zone alarm is in the keypad Status List. The relay resets
whenever a Sensor Reset is performed to remove all Fire and Fire Verify zone alarms from the Status
List. Leave this field empty to prevent the door access relay at this address from releasing during a
fire alarm.
Output Group: This option allows the output group (relays) assigned to the user profile to turn ON
when the device relay is activated for the programmed strike time. This could be used to operate an
elevator control. See the User Profiles section of the XR500/XR100 User's Guide (LT-0683), the XR150/
XR350/XR550 User's Guide (LT-1278), the XR2500F User's Guide (LT-0760), or the XR200-485/485B
User's Guide (LT-0364)for more information.
Override: Select this option to allow door On/Off schedules to be overridden by the armed condition
of the system.
Checking the Override box causes the panel to ignore the ON time for a door schedule when all areas
assigned to Access Areas for this device are armed. If any area disarms after the door schedule on
time, the panel will turn on the device output. A door output that is on during a disarmed period will