number *70P555-1212, and you have NET with Call Waiting cancelled on the second line.
Caution: A call waiting cancel programmed on a non-call waiting telephone line, would prevent
communication to the central station.
XT Series (Version 103 or higher), XTL, XTLN, and XTLN-WiFi panels
Alarms: Sends Abort, Alarm, Alarm Restoral, Ambush, Exit Error, and System Recently Armed reports
to Receiver 2.
Supervisory / Troubles: Sends Supervisory, Trouble, Trouble Restoral, Force Armed, Zone Fault
reports, and Service man messages to Receiver 2.
Opening / Closing and User: Sends Opening, Closing, Door Access, Late to Close, Unauthorized
Entry, Schedule and Code changes, Zone Reset, and Zone Bypass reports by user to Receiver 2.
Test Report: Enables the panel to send the automatic recall test report to Receiver 2. The panel
sends the automatic recall test reports as determined by the programming in the Test Timer tab.
1st Phone No: Enter the primary phone number for the panel to use for communications with
Receiver 2.
2nd Phone No: Enter the secondary phone number for the panel to use for communications with
Receiver 2.
Note: All phone numbers can be up to 32 characters. You may program a 3-second delay in
the dialing sequence by entering the letter P. You may also program a dial tone detect by
entering the letter D. These characters are counted as part of the 32 allowable characters.
1st IP Address: Enter the first (primary) IP address where the panel sends network or cell messages.
The IP address must be unique and cannot be duplicated on the network. Enter all 12 digits and leave
out the periods. For example, enter IP address 192.168.0.250 as 192168000250. The periods display
automatically.
Note: For Network: The first and second IP addresses are alternately used for 8-second
intervals until successful communication or 1 minute elapses.
1st IP Port: Enter the first IP port number to be used in conjunction with the First IP Address. The IP