Specifications
© 2015 Digital Monitoring Products
Panel B: On the third day of the seven day Test Frequency cycle, Panel B sends a signal to the
receiver. The automatic recall test is not sent to the receiver because Panel B has communicated
with the receiver during the programmed Test Frequency cycle. The seven day cycle is restarted
at the time the signal is received.
Note: These two fields, Defer Test and Test Frequency, should have the same value as the
Auto Recall Frequency and Allow Test Deferrals fields in File > Panel Information > Extended
Panel Information.
Program > Comm unicatio ns > Receiver 1 Tab
Alarms: Sends Abort, Alarm, Alarm Restoral, Ambush, Exit Error, and System Recently Armed reports
to Receiver 1.
Supervisory Troubles: Sends Supervisory, Trouble, Trouble Restoral, Force Armed, Zone Fault
reports, and Serviceman Messages to receiver 1.
Opening / Closing and User: Sends Opening, Closing, Door Access, Late to Close, Unauthorized
Entry, Schedule and Code changes, Zone Reset, and Zone Bypass reports by user to Receiver 1.
Note: Door Access is a separate option when programming the XR150/XR350/XR550 Series,
XR500 Series, XR100 Series or XR200-485 panel.
Test Report (XR20/XR40/XRSuper6): Enables the panel to send the automatic recall test report
to Receiver 1. The panel sends the automatic recall test reports as determined by the programming in
the Test Timer tab.
Test Timer (XR150/XR350/XR550 Series/XR500 Series/XR2500F/XR100 Series): Sends the
automatic recall test report to Receiver 1. The panel sends the automatic recall test reports as
determined by the programming in the Test Timer tab. Not Available on XT Series panels.
Backup: Enables Receiver 1 to serve as a backup for Receiver 2 if Receiver 2 does not respond to
communication attempts by the panel. Not Available on XT Series panels.
Door Access (XR150/XR350/XR550 Series, XR500 Series, XR100 Series, and XR200-485
only): Sends door access granted reports to Receiver 1.