Specifications

© 2015 Digital Monitoring Products
Connection: Select
the Communication
Type for the panel.
Other: Select the
panel's Main
Account Number,
the Transmission
Delay, and Events
Manager.
Second Line: Select
the backup
communication type
for the panel.
Program > Comm unicatio ns > M ethod Tab
Communication Type: Select the communication format you want the panel to use when contacting a
receiver. The panel uses the format you select for sending alarm, trouble, and supervisory reports to
the receivers programmed under the Receiver 1 and Receiver 2 tabs.
Note: Refer to Account Number Conventions for information about account numbers and
communication types.
The options available for Communication Type are listed below:
None: Select None when you are programming local systems. Selecting None ends
communications programming. When Main Communication is set to None and there is an
unrestored system trouble, the keypad sounds every day at 10:00 am.
Contact ID (CID): Select Contact ID for communication to DMP SCS-1R receivers using the
Ademco Contact ID format.
Host/Net (HST/NET): Allows the panel to communicate using asynchronous communication
through a Network Interface Card. The panel transmits the DMP Host Output reporting format