Inc. Smoke Alarm User Manual

XR2500F Installation Guide Digital Monitoring Products
29
InstallatIon
Area Information
26.1 Ownership
The control unit system shall be under one ownership.
26.2 Annunciation
TheSystemshallbeinstalledsothatwhenarminganyareafromanykeypad,thelocalbellshallannunciate.
26.3 Trouble Display
TheStatusListprogrammingshallbesettoannunciatealltroublemessagesatallkeypads.
26.4 Closing Wait
TheClosingWaitoptionmustbeprogrammedYES.
26.5 Local Bell Supervision
Whenalocalbellisemployed,thepowersupplyforthebellshallbeunder24-hourprotection.Proper
personnelformaintenanceorsecurityofthesystemshallbeabletodisarmthatarea.
Household Burglar-Alarm System Units
ANSI/UL 1023
27.1 Audible Devices
Atleastonelistedaudibledevice(AdemcoAB12M)ratedtooperateoverthevoltagerateof11.7VDCto
12.8VDCandratedat85DBminimummustbeused.
27.2 Auxiliary Circuits
Atleastoneburglaryalarminitiatingdeviceshallbeusedonthesystem.Ifthevoltageforthedeviceis
appliedbythecontrolunittheburglaryalarminitiatingdeviceshallberatedtooperateovertherangeof
11.5VDCto12.7VDC.
27.3 Bell Cutoff
TheBellCutofftimecannotbelessthanveminutes.
27.4 Entry Delay
The maximum entry delay used must not be more than 45 seconds.
27.5 Exit Delay
Themaximumexitdelayusedmustnotbemorethan60seconds.
27.6 Weekly Test
The product should be tested weekly.
27.7 Wireless Audible Annunciation Option
TheWirelessAudibleoptionmustbeselectedasDAYforresidentialapplications.
Central-Station and Proprietary Burglar-Alarm Units
ANSI/ UL 1610 AND ANSI/UL 1076
28.1 Opening/Closing Reports
TheOpening/ClosingReportsoptionmustbeprogrammedasYES..
28.2 Closing Wait
TheClosingWaitoptionmustbeprogrammedYES.
28.3 Entry Delay
Themaximumentrydelayusedmustnotbemorethan60seconds.
28.4 Exit Delay
Themaximumexitdelayusedmustnotbemorethan60seconds.