Troubleshooting guide

12
Output Information
305 Dry Contact Relays
Single pole, Double throw
Rated at 1 Amp @ 30 VDC resistive
May be activated by any of the following:
Zone condition (open or short)
Output schedule
Manually from User Menu
Communication Fail
Armed Area annunciation
Fire Alarm or Fire Trouble
Other system conditions.
See XR200 Programming Guide (LT-0196)
Voltage Outputs 3 – 10
Voltage outputs are available on XR200, XR2400F and XR200/485 Command Processor™
only.
12 VDC
50mA resistive
Activated by same conditions as 305 Dry Contact relay outputs
Annunciator Outputs
Available on XRSuper6, XR6/XR10, XR20, XR40, XR500 Command Processors™ and Output
Expander Model 716.
Switch to GROUND when activated
DO NOT provide voltage
50mA resistive
Activated by same conditions as Model 305 Dry Contact Relay and
Voltage outputs
Command Processor™ Models Output Numbers
XRSuper6, XR6/XR10, XR20 & XR40 1 – 4
XR500 3 - 6