Troubleshooting guide
9
Things to Know
The following sections provide some information that is very helpful when troubleshooting a
problem.
DMP Feature Codes
All XR series Command Processors™ use a numeric code to access certain features. Some of
these features include on-board programmer menu, diagnostic menu and the walk-test
function.
To make them easy to remember, these codes have a word-equivalent that can be spelled
out using the keys on the keypad.
DMP Feature Code Spells DMP Models
Programmer Menu 6653 P-R-O-G ALL XR series panels
Diagnostics Menu 2313 D-I-A-G XR200 and XR500 series only
One-Man Walk Test 8144 W-A-L-K XR200 and XR500 series only
Common Voltages
These operating voltages are the same across the entire XR series Command Processor™
product-line:
• AC input (terminals 1 and 2) – 17.3 VAC
• Charging circuit output (terminals 3 and 4) – 13.9 VDC
• Aux. power output (terminals 7 and 10) – 13.8 VDC
• Panel data receive output YELLOW (terminals 8 and 10) – approx. 4.5 VDC
• Panel data transmit output GREEN (terminals 9 and 10) – approx. – 3.5 VDC
Operational Parameters for Panel Zones 1 – 8*
Zone Condition Resistance on Zone Voltage on + Terminal
OPEN More than 1300 Ohms Above 2.0 VDC
NORMAL 600 – 1300 Ohms 1.2 – 2.0 VDC
SHORT Less than 600 Ohms Below 1.2 VDC
* TECH NOTE: Zones 1 – 9 for DMP XR6, XR10, XRSuper6, XR20 and XR40 Command
Processors™.
-NOTES-
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________