Specifications
INTRUSION/ACCESS/FIRE/INTEGRATED SYSTEM
PERFORMANCE SPECIFICATION FOR DMP MODEL XR150/XR350/XR550 SERIES
XR150/XR350/XR550 Intrusion/Access/Fire Detection Specification 5
4.7 Power Supplies
A. Power supplies for the control unit shall operate from 120 VAC, supplied at the respective protected areas. Standby
batteries shall be supplied to power the system in the event of a utility power failure. Batteries shall be sized to
provide 105% capacity for eight hours. Standby batteries shall be sealed lead-acid. Power supplies shall be all Solid
State.
B. Controls shall be designed to maintain full battery charge when alternating current is available. Batteries shall be
recharged to 85% capacity within 24 hours from battery use. The system shall be automatically transferred to battery
power upon loss of alternating current power and return to alternating current power upon restoration. Intrusion alarms
shall not be initiated during switch over; a signal shall be initiated upon failure of battery or alternating current power.
C. Approved power supplies shall meet or exceed the following power supply model specifications:
UL Listed DMP 505-12: 12VDC 5 Amp with transformer and enclosure.
4.8 Software
A. The system shall interface with computer software with the capability to fully program the panel by connecting to the
panel through:
Direct cable connection interface card
Receiver phone line connection
Standard phone line connection
Ethernet network connection
Network connection across the Internet
Cellular network connection using the 263C or 263H Cellular Communicators
B. The system shall interface with computer software capable of locking down all controlled doors.
C. The system shall interface with computer software capable of monitoring and logging all events.
D. The system shall interface with computer software capable of exporting reports in the following file formats:
Excel spreadsheet (*.xls Text (*.txt)
Rich Text (*.rtf) Comma-separated (*.csv)
Windows Metafile (*.wmf) HTML document (*.htm)
QuickReport (*.qrp)
E. The system shall interface with computer software capable of printing custom, filtered reports including:
All Events Door Access Granted
Zone Action Door Access Denied
Arming/Disarming Opening/Closing Schedule Changes
Area Late to Close System Monitors
User Code Changes System Events