Specifications
INTRUSION/ACCESS/FIRE/INTEGRATED SYSTEM
PERFORMANCE SPECIFICATION FOR DMP MODEL XR150/XR350/XR550 SERIES
XR150/XR350/XR550 Intrusion/Access/Fire Detection Specification 21
11.0 ACCESS CONTROL SPECIFICATIONS
11.1 Access Control Standards
The access control system shall be listed as a Power Limited Device and be listed under the standards below. Each system
shall be supplied with complete details on all installation criteria necessary to meet all of the listings.
Access Control Listings U.S. Government Standards
UL 294 Access Control System Units
Meets ICD/ICS 705 Chapter 7 Intrusion
Detection Systems (IDS)
Meets DoD/NIST SCIF Standards
11.2 Keypad
A. The system shall display a message at any keypad when any system area remains disarmed past the scheduled closing
time. The message shall be displayed at one minute past the scheduled closing time. A pre-warn tone shall also begin
sounding. If the system is not armed or a schedule extended within ten minutes past the scheduled closing time, the
system shall provide the option of sending a Late to Close report to the central station.
B. The keypad shall include a door strike relay capable of sending a report to the central station when activated.
C. The keypad shall be capable of proximity arming and disarming functions.
D. The keypad shall display red backlighting when in alarm condition notifying an individual of an unacknowledged alarm
condition.
E. The keypad shall annunciate when canceling an alarm condition the words “Cancel” or “Verify” to allow the end user
the ability to cancel a user generated alarm or to select verify to send a message to the central station that the alarm
has been verified by the end user and to send emergency response personnel. This is to comply with Alarm Verification.
11.3 Area Access Control
A. The system shall be capable of integrating area access control capability where specified into the same control panel
with the ability to have up to 10,000 user credentials. User access is limited to custom profiles and/or schedules. Anti-
passback shall be available. The networked version shall support a Two-Man Rule feature. The system shall support up
to sixteen (16) access doors, connected to the system using a manufacturer-approved interface module.
B. Area door access products shall meet or exceed features offered by the following products:
Keypad reader/administration device – DMP Model 7063/7063A, 7073/7073A, 7163/7173, 7872, 7873
Wiegand Interface – DMP Model 734, 734N, or 734N-WIFI
Reader – DMP Model PP-6005B, Model PR-5455, Model MP-5365
Cards or credentials – DMP Model 1326, DMP Model 1306P, DMP Model 1346, DMP Model 1386
11.4 Access Control Equipment
Access Control equipment shall communicate to the system by way of the control panel keypad bus. The equipment shall
have a three (3) year warranty and meet or exceed features offered in the products listed in Section 11 of this
document.