Specifications

20 XR150/XR350/XR550 Intrusion/Access/Fire Detection Specification
10.0 BURGLARY CONTROL SPECIFICATIONS
10.1 Burglary Standards
The Burglary system shall be listed as a Power Limited Device and be listed under the standards below. Each system shall
be supplied with complete details on all installation criteria necessary to meet all of the listings.
Burglary Listings Canadian Burglary Listings
UL 1023 Household Burglar Alarm System Units ULC C1023 Household Burglar Alarm System Units
UL 1076 Proprietary Burglar ULC/ORD-C1076 Proprietary Burglar
UL 1610 Central Station Burglar Alarm Units ULC S304 Central Station Burglar Alarm Units
UL 1635 Digital Burglar Alarm Communicator System
Units
U.S. Government Standards
Meets ICD 705 Chapter 7 Intrusion Detection Systems
(IDS)
Meets DoD/NIST SCIF Standards
Meets ANSI/SIA CP-01-2010 False Alarm Reduction
10.2 Area System Mode
A. The system user shall be capable of selectively arming and disarming any one or more of 32 areas within the intrusion
detection system based on the user PIN code and/or keypad used. Each of the 574 zones shall be able to be assigned to
any of the 32 available areas. The system shall be capable of having up to a thirty-two (32) character length name
programmed for each area.
B. The system user shall be capable of assigning an opening and closing schedule to all areas or to each of the 32 areas
separately. Each area shall be able to arm or disarm automatically by a schedule. The system shall have the capacity
for common areas that automatically disarm when any other area disarms and that automatically arm when all others
areas arm.
C. The networked system shall have the ability to comply with Bank Safe & Vault application. The networked system shall
also have the ability to use a two-man rule for disarming or allowing door access to an area. The system shall have the
ability to operate a Common Area application.
D. The Encrypted system shall have the feature of Card Plus Pin by area High security card access is provided by the Card
Plus Pin feature that requires both a card read and a PIN (4-6 digit user ID) entry for arming/disarming and access by
area. This Card Plus Pin operation complies with the ICPG 705 requirement for dual id authentication and operates with
a DMP Prox Keypad and a HID ProxPro reader with the keypad connected to a DMP Wiegand Interface module.
10.3 Home/Sleep/Away Mode
The system shall be capable of being configured in a Home/Sleep/Away configuration for Residential applications. The
system shall consist of a Main House system and up to two Guest House systems within one single control Panel with
each house being controlled with its own keypad as if it were separate alarm systems.
10.4 All/Perimeter Mode
The system shall be capable of being configured into the All/Perimeter configuration to enable the selective arming of
both the interior and perimeter when armed “All” or arming just the perimeter devices if arming “Perimeter”.
10.5 Zones
The system shall have a minimum of eight (8) grounded burglary zones available from the control panel, and two floating
ground powered zones for two wire type compatible smoke detectors. The system shall have the ability to expand using
the panel’s keypad bus for up to sixty-four additional zones. The system shall also have five built-in zone expansion bus
(LX500 – LX900) for an additional 500 zones of expansion. The system shall have the ability to integrate up to 500
wireless zones for a total of 574 zones overall.
10.6 Burglary Equipment
Burglary detection equipment shall communicate to the system by way of the control panel loop expansion bus or 900MHz
bi-directional spread spectrum receiver. The detection equipment shall have a three (3) year warranty and meet or
exceed features offered in the products listed in Section 11.0 of this document.
10.7 Z-Wave Equipment
The system shall be capable of 232 Z-Wave devices by means of the use of the model 738Z module. The system shall have
the capability of up to 20 Z-Wave favorites for grouping Z-Wave devices into a favorite response or control.