Specifications
INTRUSION/ACCESS/FIRE/INTEGRATED SYSTEM 
PERFORMANCE SPECIFICATION FOR DMP MODEL XR150/XR350/XR550 SERIES 
XR150/XR350/XR550 Intrusion/Access/Fire Detection Specification  19 
9.0  FIRE CONTROL SPECIFICATIONS 
9.1 FACP Standards 
The Fire Alarm Control Panel (FACP) system shall be listed as a Power Limited Device and be listed under the standards 
below. Each system shall be supplied with complete details on all installation criteria necessary to meet all of the 
listings. 
Fire Listings  Additional Listings 
UL 864 Control Units for Fire Protective Signaling 
Systems 
NFPA 70 National Electric Code (NEC) 
UL 985 Household Fire Warning  NFPA 72 Local Protective Signaling 
Related Standards  NFPA 72 Remote Station Protective Signaling 
California State Fire Marshal  NFPA 72 Proprietary Protective Signaling 
New York City FDNY COA #6167  NFPA 72 Household Fire Warning 
Canadian Fire Listings 
ULC S545 Household Fire   
ULC S559 Fire Signal Receiving Centres and Systems   
9.2 Keypads 
A. The control unit shall be completely programmable remotely using remote annunciators, and/or using 
upload/download software that communicates using SDLC 300 baud, 2400 baud, 9600 baud, IP Addressed data network, 
or cellular communications network. On-site programming from a personal computer shall also be permitted. 
Programming changes shall comply with NFPA 72 for acceptance or re-acceptance testing. 
B. The system shall include a menu selected “SENSOR RESET” option. This option shall operate without disarming and re-
arming the fire system, with use of any pass code or function key controlled by a key switch, shall reset smoke 
detectors after they have been tripped. 
9.3 Zone Configuration 
A. The FACP system shall have a minimum of two (2) Class B ungrounded 2-wire smoke detector zones available from the 
control panel. 
B. The system shall be capable of providing a maximum of 562 independent, 2-wire, and 12 VDC powered zones to power 
smoke detectors. 
C. Zones on the digital SLC shall support the CleanMe™ feature in Sentrol® smoke detectors that causes the smoke 
detector to send a message to the control panel when detection capability has deviated from the UL sensitivity range or 
has failed its internal diagnostic test. 
9.4 Fire Annunciators 
A. If at any time a remote annunciator does not detect polling from the intrusion detection/access control or FACP, the 
remote annunciator shall indicate “SYSTEM TROUBLE” on its alphanumeric LCD display within 200 seconds. If at any 
time the remote annunciator detects polling, but not for its particular address, the alphanumeric display shall indicate 
“NON-POLLED ADDR”. 
9.5 Annunciation Lamps/LEDs 
A. Visual Annunciatiors used on Annunciator modules and elsewhere throughout the system shall be either electric lamps 
or light emitting diodes (LEDs or LCDs). Annunciators shall be so connected in the circuit that Annunciator failure, 
socket or protective circuitry shall not result in improper or indeterminate signal. Lamps of varying types, voltage, and 
wattage shall have bases and sockets that prevent incorrect placement. 
9.6 Fire Control Equipment 
A. Fire Control detection equipment shall communicate to the system by way of the control panel loop expansion bus or 
900MHz bi-directional spread spectrum receiver. The detection equipment shall have a three (3) year warranty and 
meet or exceed features offered in the products listed in Section 11.0 of this document. 










