Specifications
18  XR150/XR350/XR550 Intrusion/Access/Fire Detection Specification 
8.0  Must meet ANSI/SIA CP-01-2010 Standards for False Alarm Reduction 
The system shall be capable of meeting ANSI/SIA CP-01-2010 Standards for False Alarm Reduction. 
8.1 Shall Meet Exit Delay Standards 
  Default – 60 seconds (Minimum 45 seconds) 
  Progress Annunciation – different sound last ten seconds of delay 
  Automatic Restart of running exit delay, one time upon re-entry 
  Recent Closing – signal sent if alarm within 2 minutes of Exit time expiration (change from 5 min) 
  Exit Error – Immediate local alarm and entry delay starts 
8.2 Shall Meet Entry Delay Standards 
  Default – 30 seconds (Minimum 30 seconds) 
  Pre-Warning Silenced – after first digit code entry 
  Cancel Message sent if disarmed after alarm sent 
8.3 Shall Meet Fail-to-Exit Standards 
When perimeter and exterior areas are defined and the user does not leave the building before the system arms, the 
system only arms the perimeter and leaves the interior unarmed 
8.4 Shall Meet Automatic Restart Standards 
The system shall stop the Exit countdown once and restart it to allow the user to pick up a forgotten jacket or briefcase 
and exit the building without sending an alarm to the central station. 