Specifications
14 XR150/XR350/XR550 Intrusion/Access/Fire Detection Specification
6.0 INTEGRATED INTRUSION ALARM AND ACCESS CONTROL OPERATION
6.1 Access Authority Levels
The system shall be capable of programming access credentials authority levels to check whether the user has access to a
specific area and also has the authority to disarm or arm the area. If the user access credential has access and
disarm/arm authority the system shall provide the user the option to disarm the area simultaneously upon opening the
door, or to open the door and begin an entry delay timer. With the timer option the user then disarms the area using an
intrusion control keypad inside the area. If the user only has access authority to the area and the area is in an armed
condition, the user is denied access to the area.
6.2 Door Open Schedule Override
The system shall be capable of programming certain area doors to be scheduled to unlock and lock at specific times of
the day or night. The lock/unlock function shall be capable of an override option depending upon the area
armed/disarmed status. If the area remains in an armed status at the scheduled unlock time the armed status overrides
the unlock schedule ensuring the doors remain locked and armed in situations where the business might open late, close
early, is affected by inclement weather, or another emergency.
6.3 Common Area
The system shall be capable of programming a common area to be armed when the last area in the system is armed and
disarmed when the first area in the system is disarmed. To ensure the common area works properly it shall not have any
user codes assigned to the common area. The system shall also be capable of programming multiple common areas.
6.4 Area Access Control
A. The system shall be capable of integrating area access control capability where specified into the same control panel
with the ability to have up to 10,000 user credentials. User access is limited to custom profiles and/or schedules. Anti-
passback shall be available. The networked version shall support a Two-Man Rule feature. The system shall support up
to sixteen (16) access doors, connected to the system using a manufacturer-approved interface module.
B. Area door access products shall meet or exceed features offered by the following products:
Keypad reader/administration device – DMP Model 7063/7063A, 7073/7073A, 7163/7173, 7872, 7873
Wiegand Interface – DMP Model 734, 734N, or 734N-WIFI
Reader – DMP Model PP-6005B, Model PR-5455, Model MP-5365
Cards or credentials – DMP Model 1326, DMP Model 1306P, DMP Model 1346, DMP Model 1386
6.5 Access Control Equipment
Access Control equipment shall communicate to the system by way of the control panel keypad bus. The equipment shall
have a three (3) year warranty and meet or exceed features offered in the products listed in Section 11.5 of this
document.
6.6 Early Morning Ambush (XR550 only)
A. The system shall be capable of programming an area to require two user codes be entered within a programmed
number of minutes to prevent an ambush message from being sent to the Central Station Receiver. If both user codes
are not entered within the time an ambush message is sent to the central station receiver.
B. Both user codes shall have the authority to disarm the specific area and must be entered at the same keypad or
reader. The keypad shall not display any indication that the ambush timer is running.
C. The system shall be capable of programming an output to provide an external indicator that an ambush situation is
taking place.
6.7 Two-Man Rule (XR550 only)
The system shall be capable of programming an area to require two separate user codes be entered in order to disarm
and/or allow access to a specific area. Both required codes shall have at least the same or greater authority level. Both
required codes shall be entered within 30 seconds or an alarm shall activate.
6.8 UL Bank Safe & Vault Operation (XR550 only)
The system shall be capable of being programmed to only be disarmed during scheduled times regardless of the authority
level of any user code or user profile in the system. The schedule and time and date set for this area shall not be
capable of being changed while the area is armed. Zones assigned to Bank Safe and Vault areas shall not be able to be
bypassed or force armed.