Specifications

10 XR150/XR350/XR550 Intrusion/Access/Fire Detection Specification
5.0 FUNCTIONAL DESCRIPTIONS
5.1 System Description
A. The system areas and zones shall be programmable, and the system shall store, log, display, and transmit specific
custom designations for system areas, zones, and user names.
B. To ensure continued, one-call support, the system shall be constructed of sensing components provided directly by the
system manufacturer, such as power supplies, motion detectors, door and window position switches, glass break
detectors, or other sensing devices that the manufacturer offers.
C. The system controller, user interfaces, zone input devices, relay output devices, and the system signal receiving
equipment shall be engineered, manufactured, assembled, and must be distributed from a location within the United
States of America.
D. The system shall support user interaction by way of a keypad, web browser, system software, key switch, or radio
frequency wireless control, Text messaging, or Smart Phone Application using integrated or auxiliary devices provided
by the system manufacturer.
E. The system shall support controller zone input connections, system keypads, system zone expansion modules, and
wireless zone input modules, and must support zone input connections by way of at least two competitive products.
The system shall offer a seamless integrated compatibility with hard-wire and/or wireless zone expansion equipment
for at least 500 wireless zones and/or a maximum of 574 hardwired zones.
F. The system shall be capable of offering up to five zone expansion buses, each of which can support the connection of
up to 15,000 feet of four-wire cable. Zone expansion and keypad data buses that exceed 2,500 feet of cable must
include splitter/repeater modules to boost data voltage and maintain data integrity.
G. The system shall provide a seamless capability to provide up to 506 addressable relays, which can be located at any
connection location upon a zone expansion bus.
H. System relay outputs shall have the capability of being triggered as a result of a command from the user interface,
changes in system status, changes in zone status, or by a programmable schedule.
I. System relay output states shall be programmable for momentary, maintained, pulsed, or must follow the state of an
associated system zone input.
J. The system shall be completely programmable either locally from a keypad or remotely through a standard dial-up,
and network connections by way of a LAN, WAN, and/or by way of the Internet, cellular communications paths.
K. The control unit shall be completely programmable remotely using remote annunciators, and/or using
upload/download software that communicates using SDLC 300 baud, 2400 baud, or IP Addressed data network. On-site
programming from a personal computer shall also be permitted.
L. The control unit shall be equipped with an anti-reversing circuit breaker to prevent damage due to accidental reversal
of battery leads.
5.2 Input/output Capacity
A. This system shall be capable of monitoring a maximum of 574 individual zones and controlling a maximum of 506
output relays.
B. The control panel shall have, as an integral part of the assembly, 2 SPDT Form C relays rated at 1 Amp at 30 VDC and
four open collector 12 VDC outputs rated at 50mA each. It shall also have the capacity of a maximum of 125 output
expander modules with 500 switched ground, open collector outputs, 50mA maximum and 506 auxiliary relays (Form C
rated at 1.0 Amp at 30 VDC).
C. The panel shall also provide 99 programmable output profiles for schedules, and include an integral bell alarm circuit
providing at least 1.5 Amps of steady, pulsed, or temporal bell output. Output type shall be programmable by zone
type. Relays and voltage outputs shall be capable of being independently programmed to turn on and/or off at selected
times each day.
D. The system shall be capable of supporting and controlling up to 232 Z-Wave devices and up to 20 Z-Wave Favorites for
group control.
5.3 User/Authorization Level Capacity
The system shall be capable of operation by 10,000 unique Personal Identification Number (PIN) codes with each code
having one (1) of ninety-nine (99) custom user profiles. This allows for limitation of certain functions to authorized
users. The operation of all keypads shall be limited to authorized users.