Specifications

20 XR100/XR100N Intrusion/Access/Fire Detection Specification
11.0 ACCESS CONTROL SPECIFICATIONS
11.1 Access Control Standards
The access control system shall be listed as a Power Limited Device and be listed under the standards in the table
below. Each system shall be supplied with complete details on all installation criteria necessary to meet all of the
listings.
Access Control Listings U.S. Government Standards
UL 294 Access Control System Units Meets ICD/ICS 705 Chapter 7 Intrusion Detection
Systems (IDS)
Meets DoD/NIST SCIF Standards
11.2 Keypad
A. The system shall display a message at any keypad when any system area remains disarmed past the scheduled
closing time. The message shall be displayed at one minute past the scheduled closing time. A pre-warn tone shall
also begin sounding. If the system is not armed or a schedule extended within ten minutes past the scheduled closing
time, the system shall provide the option of sending a Late To Close report to the central station.
B. The keypad shall include a door strike relay capable of sending a report to the central station when activated.
C. The keypad shall be capable of proximity arming and disarming functions.
D. The keypad shall annunciate when canceling an alarm condition the words “Cancel” or “Verify” to allow the end
user the ability to cancel a user generated alarm or to select verify to send a message to the central station that the
alarm has been verified by the end user and to send emergency response personnel. This is to comply with Alarm
Verification.
11.3 Area Access Control
The system shall be capable of integrating area access control capability where specified into the same control panel
with the ability to have up to 10,000 user credentials. User access is limited to custom profiles and/or schedules.
Anti-passback shall be available. The system shall support up to eight (8) access doors, connected to the system
using a manufacturer-approved interface module.
Area door access products shall meet or exceed features offered by the following products:
Keypad reader/administration device – DMP Model 7063/7063A, 7073/7073A, 7163/7173, 7872, 7873
Wiegand Interface – DMP Model 734, 734N, or 734N-WIFI
Reader – DMP Model PP-6005B, Model PR-5455, Model MP-5365
Cards or credentials – DMP Model 1326, DMP Model 1306P, DMP Model 1346, DMP Model 1386
11.4 Access Control Equipment
Access Control equipment shall communicate to the system by way of the control panel keypad bus. The equipment
shall have a three (3) year warranty and meet or exceed features offered in the products listed in Section 12.0 of
this document.