Specifications
2  XR100/XR100N Intrusion/Access/Fire Detection Specification 
2.0 SCOPE 
2.1 Requirements 
A.  Furnish and install a complete Intrusion Detection/Access Control system or Fire Alarm Control Panel (FACP) with 
the performance criteria detailed in this specification. The system shall be inclusive of all necessary functions, 
monitoring, and control capability as detailed herein and on accompanying Shop drawings. 
  On-site or remote video monitoring 
  Heating, air conditioning, and lighting management 
  Temperature threshold detection and monitoring 
  Humidity threshold detection and monitoring 
  Pressure threshold detection and monitoring 
  Power loss detection and monitoring, generator switching 
  Leak detection and monitoring 
  Carbon Monoxide detection and monitoring 
  Tank level threshold detection and monitoring 
B.  This specification document provides the requirements for the installation, programming, and configuration of a 
complete DMP Panel. This system shall include, but not be limited to: 
  Control panel 
  System cabinet 
  Power supply 
  Digital Signaling Line Circuits (SLC) 
  Notification Appliance Circuits (NAC) 
  Annunciator/keypad bus 
  Batteries 
  Wiring 
  Conduit 
  Associated peripheral devices 
  Other relevant components and accessories required to furnish and install a complete and operational addressable 
reporting Life Safety System. 
2.2 Standards 
The system shall be listed as a Power Limited Device and be listed under the standards in the table. Each system shall 
be supplied with complete details on all installation criteria necessary to meet all of the listings. 
Burglary Listings  U.S. Government Standards/Listings 
UL 1023 Household Burglar Alarm System Units Meets ICD 705 Chapter 7 Intrusion Detection Systems 
(IDS) 
UL 1076 Proprietary Burglar  Meets DoD/NIST SCIF Standards 
UL 1610 Central Station Burglar Alarm Units Related Standards
UL 1635 Digital Burglar Alarm Communicator System 
Units 
NFPA 70 National Electric Code (NEC) 
Fire Listings  NFPA 72 Local Protective Signaling 
UL 864 Control Units for Fire Protective Signaling 
Systems 
NFPA 72 Remote Station Protective Signaling
UL 985 Household Fire Warning  NFPA 72 Proprietary Protective Signaling
California State Fire Marshal  NFPA 72 Household Fire Warning 
New York City FDNY COA #6167  Canadian Burglary Listings 
Access Control Listings  ULC C1023 Household Burglar 
UL 294 Access Control System Units  ULC/ORD-C1076 Proprietary Burglar 
NIST  ULC S304 Central Station Burglar 
Validated XR100E Encrypted Panel  Canadian Fire Listings
  ULC S545 Household Fire 
  ULC S559 Fire Signal Receiving Centres and Systems
2.3 Americans with Disabilities 
All indicating and notification appliances shall comply with the Americans with Disabilities Act (ADA) requirements. 