Specifications

XR100/XR100N Intrusion/Access/Fire Detection Specification 15
7.0 FALSE ALARM REDUCTION FEATURES
The system shall be capable of providing false alarm reduction features, functions, capabilities, or processes that
either require alarms be verified or potential alarms be corrected before a system or zone can be placed into an
armed state.
7.1 Exit Error Alert and Reporting
The panel shall be able to provide an automatic function to prevent a false alarm from occurring if an exit door does
not properly close after the system is armed.
7.2 Entry and Exit Delay Annunciation
A. When arming, the system shall provide clear annunciation indicators to the user about the need to exit the
premises prior to the exit delay time expiring.
B. When disarming, the system shall notify the user the need to disarm the system prior to the entry delay time
expiring.
7.3 Remote Annunciation
The system shall be able to provide entry and exit delay time period notification. This notification can be from DMP
keypads, remote annunciators, or bell tests.
7.4 Abort Reporting
The system shall be capable of sending an Abort report to the central station if the system is disarmed while the alarm
is still sounding. The Abort report shall be sent after the alarm report to notify the central station that an authorized
user has cancelled the alarm.
7.5 System Testing
The system shall offer testing features that are simple, quick, and complete and provide the highest measure of safety
by ensuring that alarm conditions are detected and communicated to the proper authorities in a timely manner and
on a regularly scheduled basis.
7.6 Ambush Code
The system shall offer ambush codes for those dangerous encounters where the user is instructed to either arm or
disarm the system under threat of harm. The duress code shall disarm the system without giving local indication of
an alarm that might put the user well-being in jeopardy.
7.7 Two-Button Panic Feature
The system shall support DMP keypads that provide the option to use only two-button panic codes. The user shall be
required to press and hold two designated keys for approximately two seconds before the system generates a panic
alarm.
7.8 Fire Verify Zones
The system shall support Fire Verify zones to help the panel verify the existence of an actual fire condition before it
sends an alarm report to the central station. The Fire Verify zone shall require the panel to perform a Sensor Reset
whenever a device connected to a Fire Verify zone initiates an alarm. This shall begin a verification period during
which the panel waits for a second alarm initiation. If the original zone or any other Fire Verify zone on the panel
initiates an alarm within the next 120 seconds, the panel shall recognize this as an actual alarm and send an alarm
report to the central station.
7.9 Cross-Zoning Protection
The system shall support cross-zoning as a means of requiring two device trips to occur within a short period of time
before sounding an alarm and sending an alarm report to the central station. Supported device trips shall be from
one device that trips two times, or from two devices that each trip once.
7.10 Swinger Zone Bypassing
The system shall be capable of automatically bypassing a zone if it goes into an alarm or trouble condition a specified
number of times within a one-hour period. The panel shall be able to track the number of times the zone trips while
armed and compare that against a programmed number. When that number is reached, the panel shall be able to
automatically bypass the zone. The panel shall be capable of resetting the zone when the area to which it is assigned
disarms, is manually reset from the keypad or remotely, or remains normal for one hour.