Specifications
XR100/XR100N Intrusion/Access/Fire Detection Specification  11 
5.3 User/Authorization Level Capacity 
The system shall be capable of operation by 10,000 unique Personal Identification Number (PIN) codes with each code 
having one (1) of ninety-nine (99) custom user profiles. This allows for limitation of certain functions to authorized 
users. The operation of all keypads shall be limited to authorized users. 
5.4 Keypads 
A.  The system shall support a maximum of eight (8) keypads with alphanumeric display. Each keypad shall be capable 
of arming and disarming any system area based on a pass code or Proximity key authorization. The keypad 
alphanumeric display shall provide complete prompt messages during all stages of operation and system 
programming and display all relevant operating and test data. 
B.  Communication between the control panel and all keypads and zone expanders shall be multiplexed over a non-
shielded multi-conductor cable, as recommended by the manufacturer. This cable shall also provide the power to all 
keypads, zone expanders, output expanders, and other power consuming detection devices. 
C.  If at any time a keypad does not detect polling, the alphanumeric display shall indicate "SYSTEM TROUBLE". If at 
any time two devices are programmed for the same address, the alphanumeric keypad shall display “4 WIRE BUS 
TROUBLE”. If at any time a keypad detects polling but not for its particular address, the alphanumeric display shall 
indicate "NON POLLED ADDR". The system shall display all system troubles at selected keypads with distinct 
alphanumeric messages. 
D.  The keypad shall include self-test diagnostics enabling the installer to test all keypad functions: display test, key 
test, zone test, LED test, relay test, tone test, and address test. 
E.  The keypad shall provide an easy-to-read English text display. The text shall exactly match the text seen in all 
software reports, keypad displays, and central station reports. 
F.  The keypad user interface shall be a simple-to-use, menu-driven help system that is completely user friendly. 
G.  The control panel shall support a keypad interface accessible on the World Wide Web in a browser window. The 
web-accessible keypad interface shall provide at least five (5) programmable hyperlinks for camera access or other 
use. 
5.5 Zone Configuration 
A.  A minimum of 4 Class B ungrounded zones shall be available at each keypad or zone expander on the system. The 
system shall have the capacity for a maximum of eight (8) keypads and a maximum of 25 four (4) zone expanders or 
100 single zone expanders. It shall also have the capacity of a maximum of 25 supervised relay output expanders. All 
Class B zones shall be 2-wire, 22 AWG minimum, supervised by an end-of-line (EOL) device and shall be able to 
detect open and short conditions in excess of 500ms duration. 
B.  Each zone shall function in any of the following configurations: Night, Day, Exit, Fire, Supervisory, Emergency, 
Panic, Auxiliary 1, Auxiliary 2, Fire Verification, Cross Zone, Priority, and Key Switch Arming. 
C.  The digital SLCs and the annunciator/keypad bus shall be able to operate at a maximum wiring distance of 2500 
feet from the control panel on unshielded, non-twisted cable. This distance may be extended to a total of 15,000 
feet when bus repeater modules are installed. 
D.  Each zone shall function in any of the following configurations: 
Night Supervisory Auxiliary 1 Cross-Zone
Day Emergency Auxiliary 2 Priority
Exit Panic Fire Verification Arming
Fire 