COMPLIANCE
XR5 Installation Guide Digital Monitoring Products
15
WIRING DIAGRAMS
Universal UL and NFPA Fire Alarm Specications
18.1 Introduction
The programming and installation specications contained in this section must be completed when
installing the XR5FC and XR5SL panels in accordance with any of the UL or NFPA re standards. Additional
specications may be required by a particular standard.
18.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
18.3 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is specically provided for that purpose.
18.4 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by
the end user is essential to ensure continuous satisfactory operation of any alarm system. Offering a
maintenance program and acquainting the user with the correct procedure for use and testing of the
system is also the responsibility of the installing alarm company.
18.5 Audible alarm (XR5FC only)
Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones
should not be programmed as “N”. See section 6.3A in the XR5FC and XR5SL Programming Guide (LT-0312).
18.6 UL Listed Receivers
UL has veried operation with the Sur-Gard SG-HLR2-DG, FBII CP220PB, Osborne-Hoffman Quick-Alert, and
Radionics D6500 receivers.
UL 864 and NFPA 72 Specications
Control Units for Fire Protective Signaling Systems
19.1 Power Fail delay
The Power Fail Delay option must be set to 6 hours. See section 5.4 of the Programming Guide (LT-0312).
19.2 Central Station Signaling Systems
Two phone lines must be used. The two phone lines cannot be ground start or party lines. See section 3.3
of the XR5FC and XR5SL Programming Guide (LT-0312).
Two different phone numbers must be programmed for digital communication. See sections 3.12 and 3.20
of the XR5FC and XR5SL Programming Guide (LT-0312).
19.3 Local Protective Signaling Systems
The DMP Model 865 or 866 Notication Circuit Module must be used on the bell circuit for detection of
shorts and grounds. See sections 21.1 to 21.3 of this guide.
19.4 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. Up to two 12 VDC, 7.0 Ah batteries may be used. See
section 6.6 for standby battery calculations. Two Radionics Model D127 Reversing Relay Modules may be
used to provide two reversing polarity telephone connections instead of dual phone lines. See section 21.4
and the D127 Installation Instruction sheet for wiring details.
California State Fire Marshal Specications
20.1 Bell Output Denition
The bell output of the Model XR5FC must be programmed to operate temporal on re alarms. See section
6.3A of the XR5FC and XR5SL Programming Guide (LT-0312).