Installation guide

Digital Monitoring Products XR5 Installation Guide
16
WIRING DIAGRAMS
21.2 Multiple 865 NotiÞ cation Circuit Modules
AC
1
3
+B
5
BELL
6
SMK
11
Z1A+
7
RED
8
YEL
9
GRN
10
BLK
2
AC
4
-B
12
Z1A-
13
Z1B+
14
Z1B-
15
Z2+
16
Z2-
17
Z3+
18
Z3-
19
Z4+
20
Z4-
21
Z5+
22
Z5-
N/ON/C COMN/ON/C COM
J11
1
2
3
4
J12
OUTPUT 2
OUTPUT 1
MAIN
BACKUP
Telephone
Connections
J4 J5
Silence/Reset
Header
J13
J14
Bell
Monitor
Silence/Reset
Button
Silence/Reset
Push for 1 Second
Panel
Reset
J10 Trouble Annunciator Header
Relay Sockets for Optional
Form C Outputs on J11
XR5 Commercial Fire
Command Processor Panel
S
S
3.3K EOL
Zone 2
SS
W
W
Zone 1
SS SS
3.3K EOL
Zone 3
SS
3.3K EOL
Zone 3
SS
UL Listed,
Polarized
Notification
Appliances
Style Z
Power Supply Trouble
Contacts N/C
24 VDC 5
Amp
Maximum
Power Supply
Trouble
Contacts N/C
Auxiliary
Power
Supply
+ -
S
S
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In -
6 Bell Out A +
10 Bell Trouble
11 Bell Trouble
865
Module
Normal/Silence Switch
7 Bell Out A -
8 Bell Out B +
9 Bell Out B -
Notification Circuit Module
DMP Model 865
25mA @12 VDC
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In -
6 Bell Out A +
10 Bell Trouble
11 Bell Trouble
865
Module
Normal/Silence Switch
7 Bell Out A -
8 Bell Out B +
9 Bell Out B -
Notification Circuit Module
DMP Model 865
25mA @12 VDC
24 VDC 5
Amp
Maximum
To additional 865 Notification Circuit Modules. Up to a
maximum of thirteen 865 Modules on the XR5 panels. All
modules must be installed in a 340FC, 349, or 350 Enclosure
connected by no more than 20 feet of conduit.
S = Supervised Circuit
10K EOL
DMP Model 308
UL Listed, Polarized
Notification Appliances
S
S
Each 865 Notification Appliance Circuit Module in alarm draws
up to 59mA through its Terminal 3 Alarm Input.
Note: If an auxiliary power supply is not used, terminals 3
and 4 on the 865 Module can be jumpered together to receive
Bell Power from the XR5F panel. A maximum of 1.5 Amps as
12 VDC is available from terminal 5 of the XR5F panel.
Auxiliary Power Supply must be regulated, UL Listed for Fire
Protective Signaling Service. Power Supplies must have
battery backup.
Style Y
+ -
Auxiliary
Power
Supply
S
S