SCS-1 Install/User's Guide
5 - PRINTOUT EXPLANATIONS
5.18 Explanations For Selected Supervisory Messages
WARNING: Low communication line level.
The DB level of the telephone line is still receivable but is below normal operating limits.
ALARM: Panel not responding.
The account number being polled is not responding. Possible causes are a bad phone line or faulty
communication module.
WARNING: New panel on line.
This message is sent any time the account number is changed on a Command Processor panel.
WARNING: Non-alarm message overflow.
The message buffer of the Command Processor has been filled. Some non-alarm messages have been
lost.
WARNING: Fire-Burglary trouble overflow.
The message buffer of the Command Processor has been filled. Some fire or burglary zone trouble
messages have been lost.
WARNING: Communication trouble - Line #
The line number listed received a call but a message was not transmitted.
WARNING: Loop alarm overflow.
The message buffer of the Command Processor has been filled. Some Supervisory, Emergency, Auxiliary 1
or Auxiliary 2 zone alarm messages have been lost.
WARNING: Fire zone alarm overflow.
The message buffer of the Command Processor has been filled. Some fire zone alarm messages have
been lost.
WARNING: Panic zone alarm overflow.
The message buffer of the Command Processor has been filled. Some panic zone alarm messages have
been lost.
WARNING: Burglary zone alarm overflow.
The message buffer of the Command Processor has been filled. Some burglary zone alarm messages have
been lost.
TROUBLE: Message not acknowledged.
The message(s) printed above this were received by the system but during the final acknowledge routine a
discrepancy was noted. The system did not give a final acknowledge to the panel therefore it will call again with
the same message(s).
TROUBLE: Carrier locked on line.
This message is printed on multiplex systems. If a panel on the multiplex network has its carrier tone on
steady the system will display this message and transmit a group poll in an attempt to clear the tone.
Carrier off, multiplex line restored.
This message is printed when the multiplex line is restored.
ABORT signal received.
This message is printed after a Command Processor has transmitted an alarm and the system is disarmed
before the bell cutoff delay expires.
Loop swinger automatically bypassed.
This message proceeds the listing of the zone number that has been automatically bypassed.
Loop swinger automatically reset.
This message proceeds the listing of the zone number that has been automatically reset.