SYSTEM OVERVIEW
1.1 Description
The SCS-1 Receiver system from DMP is comprised of a full featured digital/multiplex capable alarm receiver, a CRT
display for viewing incoming reports, a local 80 character printer, and a detachable keyboard for acknowledging
reports and configuring the SCS-1 system and its components.
1.2 Function
The SCS-1 Receiver system provides central stations with computerized monitoring of DMP command processor
panels. Features of the SCS-1 receiver include automatic logging of alarm, trouble, and supervisory account reports
on a local printer with the date and time of their occurrence.
1.3 CRT Display
The CRT display adds flexibility to the SCS-1 system by allowing the operator to view alarm reports before
acknowledging them from the system keyboard. A typical account report includes:
Account Number - 12345
Loop Name - FRONT DOOR, BACK DOOR
Alarm Type - Burglary, Fire, Panic
Time and Date of occurrence
All information is displayed on the CRT screen and logged on the local printer. Opening and Closing reports from
monitored accounts provide the operator with:
Account Number - 12345
Area Numbers and Names - Area: 1 OFFICE
Area: 2 STOCKROOM
User Number of Individual - Disarmed by User #25
Time and Date of Occurrence
1.4 Printer
Routine reports are logged on the printer without need of operator response while supervisory reports are logged on
the printer and displayed on the CRT console for operator acknowledgment.
1.5 Additional Reports
Other reports transmitted to the SCS-1 by DMP Command Processor panels include:
Addition and deletion of code numbers including user number of the person making the change
Bypass and reset of zones by number and name including user number of the person making the change
Schedule changes including user number of the person making the change
Trouble and Restoral report by zone name and number
Door access reports including user number and number of the door being accessed
Section 5 of this guide provides a detailed explanation of the alarm and activity reports that can be logged on the
SCS-1 printer or displayed on the CRT.
1.6 Line Capacity
The SCS-1 Receiver accommodates up to five incoming phone lines. Each SCS-1 can be configured with both digital
dialer and multiplex receiving lines. Multiplex lines have a capacity of 128 separate accounts. Digital Dialer lines have
a capacity of 65,535 separate accounts.
To select the communication type used on each incoming line, refer to Configure System in section 4.10.
1.7 24 Hour Recall Tests
The automatic recall test from a digital dialer account must be tracked manually or with a listed automation system.
The SCS-1 Receiver does not automatically indicate a delinquent recall test. Failure to receive a signal from a Digital
Alarm Communicator Panel (DACT), over a 24 hour period shall be handled as a trouble signal.