XR6A/XR10A/XR20A Command ProcessorTM Panels Installation Guide 6/10/26 Zone Burglary/Fire/Access Control Panels with Built-in Communicator ACN 087 480 279 2841 E. Industrial Drive Springfield, MO USA 65802-6310 Downloaded from: http://www.guardianalarms.
MODEL XR6A/XR10A/XR20A COMMAND PROCESSORTM INSTALLATION GUIDE COMPLIANCE STATEMENT The DMP Model XR6A, XR10A, and XR20A systems have been tested and comply with the requirements of CISPR22 Class B Electromagnetic Emissions, ACA Technical Standard TS001-1997 Electrical Safety, AS/NZS 3260-1993 including amendments 1 to 4 Electrical Safety, and ACA Technical Standard TS002-1997 Telecommunications. ACN 087 480 279 Copyright © 1995 - 1999 Digital Monitoring Products, Inc.
TABLE OF CONTENTS Section Page Panel Specifications ........................................................................................... 5 1.1 1.2 1.3 1.4 1.5 1.6 Power supply .................................................................................................... 5 Communication ................................................................................................ 5 Panel zones ..................................................................................................
TABLE OF CONTENTS Section Page Powered Zone for 2-Wire Smoke Detectors.................................................... 15 11.1 Terminals 25 and 26 ....................................................................................... 15 Annunciator Outputs ........................................................................................ 16 12.1 Description ..................................................................................................... 16 12.2 Harness wiring .............
Introduction Panel Specifications 1.1 Power supply Transformer Input: 16.5 VAC 40VA or 16.5 VAC 20VA Standby Battery: 12 VDC 7.0Ah (40VA transformer charges up to 2 batteries) Auxiliary Output: 12 VDC at 500mA Bell Output: 12 VDC at 1.5 Amps with 40VA transformer, 600mA with 20VA transformer Smoke Detector Output: 12 VDC at 100mA All circuits inherent power limited 1.
Introduction Introduction 2.1 Description The DMP XR6A/XR10A/XR20A Command Processors are powerful 12 VDC burglary and fire communicator panels with battery backup. The XR10A/XR20A provide nine on-board burglary zones and one on-board 12 VDC Class B powered fire zone. The XR6A provides five burglary and one fire zone. The fire zone has a reset capability to provide for 2-wire smoke detectors, relays, or other latching devices.
Introduction System Components 3.1 Description The DMP XR6A/XR10A/XR20A system is made up of an alarm panel with built in communicator, an enclosure, a 16.5 VAC transformer, and a 12 VDC 7.0 Ah battery. You can add up to four Security Command keypads to the system and can also connect auxiliary devices to the panel's open collector outputs to expand the basic system. Combined current requirements of additional modules may require an auxiliary power supply. Refer to section 6.
Digital Monitoring Products Page 4 Cold Water P ipe Earth Gro und M odel 692 75mA @ 8 -16 VDC M odels 690, 790, 791, 793 100mA @ 8 - 16 VDC Keypa ds M odels 670. 770, 771, 100mA @ 8 - 16 VDC 125m A with display lit Bell ZO N E 3 ZO N E 2 ZO N E 1 Up to 500m A auxiliary current at 10.4 - 13.2 VDC from Term inal 7. RED 22 GA. MIN 1K 1K Z3 1K 1K GND Z4 Z5 1K 3.
Installation Installation 4.1 Mounting the enclosure The metal enclosure must be mounted in a secure, dry place to protect the panel from damage due to tampering or the elements. It is not necessary to remove the PC board when installing the enclosure.
Installation 4.2 Mounting keypads Security Command keypads have removable covers that allow you to easily mount the base to a wall or other flat surface using the screw holes provided on each corner. For mounting keypads on solid walls, or for applications where conduit is required, use a DMP 695, 696, 775, or 776 keypad conduit backbox. 4.3 Wiring keypads Keypad data bus The keypad data bus consists of a 4-wire cable that provides 12 VDC power, data in, data out, and a panel common.
Installation Secondary Power Supply 6.1 Battery terminals 3 and 4 Connect the black battery lead to terminal 4 on the panel and to the negative terminal of the battery. The negative terminal connects to the enclosure ground internally through the XR6A/XR10A/XR20A circuit board. Connect the red battery lead to terminal 3 on the panel and to the positive terminal of the battery. Observe polarity when connecting the battery. The panel can charge up to two batteries.
Installation XR6A/XR10A/XR20A STANDBY BATTERY POWER CALCULATIONS Standby Current Command Processor Panel Active Zones 1-9 Active Zone 10 (zone 6 on XR6A) 2-Wire Smoke Detectors Qty _____ x Qty _____ x 50mA 1.6mA 4mA .1mA Alarm Current ______ mA ______ mA Qty _____ x ______ mA ______ mA Qty _____ x Bell Output 50mA *2mA 30mA .1mA ______ mA ______ mA ______ mA ______ mA 1500mA max.
Installation Bell Output 7.1 Terminals 5 and 6 Nominal 12 VDC is supplied by terminal 5 on the panel to power alarm bells or horns. The output is rated for a maximum of 1.5 Amps with a 40VA transformer and 600mA with a 20VA transformer. This output can be steady or pulsed depending upon the Bell Action specified in Output Options programming. Terminal 6 is the ground reference for the bell circuit. Keypad Data Bus 8.
Installation Burglary Zones 10.1 Description The XR10A/XR20A terminals 12 to 24 are the nine burglary zones. For programming purposes, the zone numbers are 1 to 9. The zone configurations on terminals 12 to 24 are described below. The XR6A terminals 12 to 18 are the five burglary zones with terminal 16 providing the ground for zone 5.
Installation Powered Zone for 2-Wire Smoke Detectors 11.1 Terminals 25 and 26 A resettable 2-wire Class B powered zone is provided on terminals 25 (positive) and 26 (negative) of the panel. For programming purposes, the zone number is 10 on the XR10A/XR20A and zone 6 on the XR6A. The zone uses a Model 309, 3.3k W EOL resistor (provided with the panel) and has an operating range of 8.8 to 14.2 VDC. Power is dropped from zone 10 any time a Sensor Reset is performed on the panel.
Installation Annunciator Outputs 12.1 Description The four annunciator outputs can be programmed to indicate the activity of the panel's zones or conditions occurring on the system. Annunciator outputs do not provide a voltage but instead switch to ground voltage from another source.
Installation Reset Jumpers J16 14.1 Description There are two reset jumpers located at the top right of the panel's circuit board labeled RESET. Momentarily shorting these jumpers allows you to reset the microprocessor of the XR6A/XR10A/XR20A. Resetting the panel allows you to enter the panel's internal programmer. To reset the panel when first installing the system, place the blade of a slotted screwdriver across the two reset jumpers after applying power to the panel.
Digital Monitoring Products 2841 E.