Specifications
5-4
CSO TO CIRCUIT MAPPING
PRIOR MENU to OPTIONS MENU…. Selection
4…. CSO TO CKT MAPPING
PG DWN ETC…through C/S/O page 5, combinations
9 & 10. Any of the available Time Clock Circuits can
be activated by selected combinations of cycle, split,
offset, and/or system. Specify desired C/S/O with
system/no system along with any time clock circuits
to be active. Enter the time clock circuit number
under “CKT" (up to 8 circuits per C/S/O combination.
9, 5 ,6= Don’t care states for C/S/O. 0= don’t care
state for system, 1= in system only, 2= not in system
only. For example, to inhibit MAX timing during sys-
tem operation, program C/S/O combination 1; 956/1
and the first two CKT columns 15 and 16 respect-
ively. Inhibit MAX timing will occur for any C/S/O
combination when in system operation.
COORD PH/SERV PLANS
PRIOR MENU ....Selection 4....COORD PH/SERV
PLANS
PG DWN ETC...through Cycle 7&8. Each of 8 cycles
can be accessed by paging down In order, starting
with cycle 1&2 as above. Intermediate cycle screens
can be skipped by changing the cycle number at the
top of left of the page (select cycle 1, 3, 5, 7 then
Enter). Note that changing this number does not
affect any data, only the screen displayed (i.e. Jump
from cycle 1&2 screen to cycle 7&8).
Each screen specifies the following:
Coord ph’s. Specifies the coordinated phases for
that cycle/split combination. The first digit is the ring 1
phase and the second is the ring 2 phase. Load the
second digit as a 0 if single ring (eg. 10 = phase 1,
ring 1). Note that the force off and permissive
programming for the specified cycle and split must be
consistent with the coord phases
Service plan. Specifies the service plan 0-8 (0=
none) to be implemented with that cycle/split (see
service plans).
Max plan. Specifies the max plan 0-8 (0= none) to be
implemented with that cycle/split (see max plans).
Notes:
1.Program 0’s If you do not wish to use service/max
plans or If you wish to select them strictly by clock circuit.
Cycle/Split (C/S) selection of service and max plans will
override time clock when both are active.
2. Prior to Rev 7, the LMD8000 did not have to be "in
system” for cycle/split selection of a service and/or max
plan... only that the specific cycle/split Is selected. From
LMD8000 rev 7 and higher (and all 9200 versions),
“system” must be active (coordinating). Thus, the unit will
automatically revert to Clock selection or normal NEMA
values when not in system. Prior to rev 7 this required a
return to a “dummy” cycle and split with 0’s for service
and/or max plans when In free operation.
CYCLE LENGTHS AND MAX DWELLS
PG DWN OR SELECTION 5....
Sets Cycle Lengths and Max Dwell values (0-255 secs).
Max Dwell is a setting used with Dwell mode offset seek-
ing, restricting the amount the unit can dwelt In any one
cycle (typically set 20-35% of cycle length).
OFFSET TIMES
PG DW1 from cycle lengths...
PG DWN ETC...through cycle 7 & 8.
FORCE OFFS AND PERMISSIVES
PRIOR MENU....Selection 6...FORCE OFF + PERMS
--CSO TO TIME CLOCK CKT MAPPING—
CSO/S CKT CKT CKT CKT CKT CKT CKT CKT
000/0 0 0 0 0 0 0 0 0
000/0 0 0 0 0 0 0 0 0
CYC/SP C1 S1 S2 S3 S4 |C2 S1 S2 S3 S4
COORD PH’S 26 26 26 26 | 26 26 26 26
SERVICE PL 0 0 0 0 | 0 0 0 0
MAX PL 0 0 0 0 | 0 0 0 0
--CYCLE LENGTHS—
CYCLE 1 2 3 4 5 6 7 8
LENGTH 90 100 110 120 120 120 120 120
MAX DWL 30 30 30 30 30 30 30 30
--OFFSET TIMES (0-255 SECS)--
OFF 1 OFF 2 OFF 3 OFF 4 OFF 5
CYC 1 0 0 0 0 0
CYC 2 0 0 0 0 0
--FORCE OFFS & PERMISSIVES-
1. READ OR MANUALLY LOAD
2. AUTO CALCULATE FROM PERCENTS