Owner`s manual
Page 12 1503-065-E-3-14
1.4 Circuit Board Terminal Identification
1. Input Power: 12-24 Volt AC or 12-24 Volt DC NEGATIVE
2. Input Power: 12-24 Volt AC or 12-24 Volt DC POSITIVE
3. Earth Ground
4. Request to Exit
5. Request to Exit
6. Relay Contact Normally Open (N.O.)
7. Relay Contact Normally Closed (N.C.)
8. Relay Contact Common
NOTES:
A switch closure across terminals 4 and 5 will activate the relay for its programmed strike
time.
Relay contacts are rated for 30 Volt, 1 amp maximum power.
Electric strikes and magnetic locks must be powered from their own power supply as shown
on the wiring diagram (page 11). Do not power the keypad and the locking device from the
same source.
Current Draw with 12 Volt DC Input: 20mA at rest; 105mA with relay activated.
Current Draw with 24 Volt DC Input: 45mA at rest; 130mA with relay activated.
Current Draw with 16 Volt AC Input: 86mA at rest; 225mA with relay activated.