Technical data

Manual VIPA System 200V Chapter 3 Digital input modules
HB97E - SM - Rev. 09/19 3-41
Electrical data VIPA 221-1BH20
Number of inputs 16
Counter 1 (2 inputs A, B)
Rated input voltage DC 24V (20.4 ... 28.8V)
Signal voltage "0" 0 ... 5V
Signal voltage "1" 15 ... 28.8V
Input filter time delay 3ms
Input filter counter
100ยตs
Max. impulse frequency 100kHz
Input current typ. 7mA
Power supply DC 5V via backplane bus
Current consumption
via backplane bus
85mA
Isolation 500Vrms (field voltage to the bus)
Status indicator via LEDs located on the front
Programming specifications
Input data 6byte
Output data 6byte
Parameter data 3byte
Diagnostic data -
Dimensions and weight
Dimensions (WxHxD) in mm 25.4x76x88
Weight 50g
Technical data