Technical data
Manual VIPA System 200V Chapter 3 Digital input modules
HB97E - SM - Rev. 09/19 3-25
Wiring diagram Schematic diagram
AC 240V
1
2
3
4
5
6
7
8
9
10
M
M
internal
V-Bus
Optocoupler
LED
Input-Module
AC 240V
Note!
This module is specified for voltages of max. AC 260V.
If inductive loads occur on the network, this load has to be filtered either
directly at the module or at the according device, for example by using a
snubber network.
Electrical data VIPA 221-1FF40
Number of inputs 8
Nominal input voltage AC 240V
Current consumption per channel 20mA
Signal voltage "0"
Hysterese
Signal voltage "1"
Input filter time delay
Frequency of input voltage
AC 0 ...70V
AC 90 ... 160V
AC 190 ... 260V
25ms
50Hz
Input resistance
136kΩ
Power supply DC 5V via backplane bus
Current consumption
via backplane bus
60mA
Isolation 500Vrms (field voltage to the bus)
Status indicator via LEDs located on the front
Programming specifications
Input data 1byte
Output data -
Parameter data -
Diagnostic data -
Dimensions and weight
Dimensions (WxHxD) in mm 25.4x76x88
Weight ca. 50g
Wiring and
schematic
diagram
Technical data