Technical data

Manual VIPA System 200V Chapter 9 SM 238C - Combination module
HB97E - SM - Rev. 09/19 9-29
No main counting direction:
The counter counts starting with the load value.
At over- or underrun at the count limits, the counter jumps to the
according other count limit and counts from there on.
The count limits are set to the maximum count range.
Valid value range
Lower count limit - 2 147 483 648 (-2
31
)
Upper count limit + 2 147 483 647 (2
31
-1)
Counter value - 2 147 483 648 (-2
31
) to + 2 147 483 647 (2
31
-1)
Load value - 2 147 483 647 (-2
31
+1) to + 2 147 483 646 (2
31
-2)
upper
counter limit
load value
0
gate start
time
counter value
gate stop
lower
counter limit
overflow
underflow
Main counting direction forward
The counter counts starting with the load value.
When the counter reaches the end value –1 in positive direction, it
jumps to the load value at the next positive count pulse.
Valid value range
Limit value - 2 147 483 647 (-2
31
+1) to + 2 147 483 647 (2
31
-1)
Lower count limit - 2 147 483 648 (-2
31
)
Counter value - 2 147 483 648 (-2
31
) to end value -1
Load value - 2 147 483 648 (-2
31
) to end value -2
end value
lower
counter limit
Load value
0
gate start
overflow
underflow
time
counter value
gate stop
Periodically