Technical data
Chapter 8 Analog input/output modules Manual VIPA System 200V
8-30 HB97E - SM - Rev. 09/19
... continue
Data for choosing an actuator
Output ranges (rated values)
Voltage 1 ... 5V, 0 ... 10V, ±10V
Current 4 ... 20mA, 0 ... 20mA, ±20mA
Load resistance
(in nominal range of the output)
At voltage outputs
min. 1kΩ
- capacitive load
max. 1µF
At current output
max. 500Ω
- Inductive load max. 10mH
Voltage outputs
Short-circuit protection yes
Short-circuit current max. 31mA
Current outputs
No-load voltage max. 13V
Destruction limit against
voltages/currents applied from outside
Voltage at outputs to M
ANA
max. 15V
Current max. 30mA
Connection of actuators
for voltage output 2conductor connection
for current output 2conductor connection
Parameter data
Input data 8byte (1 word per channel)
Output data 4byte (1 word per channel)
Parameter data 16byte
Diagnostic data 12byte
Dimensions and weight
Dimensions (WxHxD) in mm 25.4x76x88mm
Weight 80g
1)
The error limits are measured with a load of R=1GΩ. For voltage output the output impedance is 50Ω.
2)
The error limits are measured with a load of R=10Ω.