Technical data

Manual VIPA System 200V Chapter 8 Analog input/output modules
HB97E - SM - Rev. 09/19 8-29
... continue
Basic error limit (during temperature is 25°C, referring to output range)
Measuring range Tolerance
Voltage output 1 … 5V ±0.4%
1)
0 … 10V ±0.3%
1)
±10V ±0.2%
1)
Current output ±20mA ±0.2%
2)
0 … 20mA ±0.4%
2)
4 … 20mA ±0.5%
2)
Temperature error
(with reference to the output range)
±0.01%/K
Linearity error
(with reference to the output range)
±0.05%
Repeatability (in steady state at 25°C
referred to the output range)
±0.05%
Output ripple;
range 0 to 50kHz
(referred to output range)
±0.05%
States, Alarms, Diagnosis
Diagnosis alarm parameterizable
Diagnosis functions
- Sum error monitor red LED (SF)
- Diagnostic information readable possible
Substitute value can be applied yes
Data for choosing an encoder
Voltage input
±400mV
10M
±4V, ±10V, 1 ... 5V, 0 ... 10V
120k
Current input
±20mA, 0 ... 20mA, 4 ... 20mA
33 (90 starting with release 2)
Resistors
0...600, 0...3k 10M
Resistance thermometer
Pt100, Pt1000, Ni100, Ni1000
10M
Maximum input voltage for voltage
input (destruction limit)
25V
Maximum input current for current
input (destruction limit)
30mA
Connection of the sensor
For measuring voltage yes
For measuring current
as 2wire transmitter possible with external power supply
as 4wire transmitter yes
For measuring resistance
with 2conductor connection yes
Characteristic linearization
for RTD Pt100, Pt1000, Ni100, Ni1000
Unit for temperature measurement
°C
continued ...