Technical data

Manual VIPA System 200V Chapter 8 Analog input/output modules
HB97E - SM - Rev. 09/19 8-5
Circuit diagram Schematic diagram
1
2
3
4
5
6
7
8
9
10
L+ DC24V
M
V
A
V
A
IN
IN
OUT
OUT
V-Bus
Input / Output
µP
D
A
Channel
3
Q1
M1
D
A
Channel
2
Q0
M0
D
A
Channel
0
+0
M0
Mux
Channel 1
+0
M1
Attention!
The following circumstances may cause damages at the analog module:
The external supply of the input (current/voltage) must not be present as
long as the backplane bus of the CPU is still without current supply!
Parameterization and connection of the input must be congruent!
You must not apply a voltage >15V to the input!
Data input range:
During the measuring, the measuring values are stored in the data input
area with the following assignment.:
Byte Bit 7 ... Bit 0
0 High-Byte channel 0
1 Low-Byte channel 0
2 High-Byte channel 1
3 Low-Byte channel 1
Note!
At 3wire res. 4wire measuring, only channel 0 is used.
Data output range:
For output of the data you set a value in the data output area. The
functionality can be set by means of function-no. for each channel.
Byte Bit 7 ... Bit 0
0 High-Byte channel 2
1 Low-Byte channel 2
2 High-Byte channel 3
3 Low-Byte channel 3
Circuit and
schematic
diagram
Data input/
data output range