Technical data

Chapter 7 Analog output modules Manual VIPA System 200V
7-22 HB97E - SM - Rev. 09/19
... continue
Linearity error
(with reference to the output range)
±0.05%
Repeatability (in steady state at 25°C
referred to the output range)
±0.05%
Output ripple;
range 0 to 50kHz
(referred to output range)
±0.05%
Data for choosing an actuator
Output ranges (rated values)
Voltage 1 ... 5V, 0 ... 10V, ±10V
Current 4 ... 20mA, 0 ... 20mA, ±20mA
Burden resistance (in nominal range of the output)
at voltage outputs
min. 1k
- capacitive load
max. 1µF
at current outputs
max. 500
- inductive load max. 10mH
Voltage outputs
Short-circuit protection yes
Short-circuit current max. 31mA
Current outputs
No-load voltage max. 13V
Destruction limit against voltages/currents
applied from outside
Voltage at outputs to M
ANA
max. 15V
Current max. 30mA
Connection of actuators
for voltage output 2conductor connection
for current output 2conductor connection
States, Alarms, Diagnosis
Diagnosis alarm parameterizable
Diagnosis functions parameterizable
Sum error monitor red LED SF
Diagnostic information readable possible
Substitute value can be applied no
Programming specifications
Input data -
Output data 8byte (1 word per channel)
Parameter data 6byte
Diagnostic data 4byte
Dimensions and weight
Dimensions (WxHxD) 25.4x76x88mm
Weight 100g
1)
The error limits are measured with a load of R=1G. For voltage output the output impedance is 30.
2)
The error limits are measured with a load of R=10.