Technical data
Manual VIPA System 200V Chapter 7 Analog output modules
HB97E - SM - Rev. 09/19 7-11
... continue
Data for choosing an actuator
Output ranges (rated values)
Voltage ±10V
0...10V
Burden resistance (in nominal range of the output)
at voltage outputs
min. 5kΩ
- capacitive load
max. 1µF
Voltage outputs
Short-circuit protection yes
Short-circuit current max. 6mA
Destruction limit against voltages/currents
applied from outside
Voltage at outputs to M
ANA
max. 15V
Current max. 30mA
Connection of actuators
for voltage output 2conductor connection
States, Alarms, Diagnosis
Diagnosis alarm -
Diagnosis functions -
Sum error monitor -
Diagnostic information readable -
Substitute value can be applied -
Programming specifications
Input data -
Output data 8byte (1word per channel)
Parameter data 6byte
Diagnostic data -
Dimensions and weight
Dimensions (WxHxD) 25.4x76x88mm
Weight 100g